background image

ETC Installation Guide

Sensor IQ DALI Control Option Card

Corporate Headquarters Middleton, WI, USA +1 608 831 4116 London, UK +44 (0)20 8896 1000

Holzkirchen, DE +49 (80 24) 47 00-0 Rome, IT +39 (06) 32 111 683 Hong Kong +852 2799 1220 Paris, FR +33 1 4243 3535

Web

 

etcconnect.com

 Support 

support.etcconnect.com 

Contact 

etcconnect.com/contactETC

© 2020 Electronic Theatre Controls, Inc. Trademark and patent info: 

etcconnect.com/ip 

Product information and specifications subject to change. ETC intends this document to be provided in its entirety.

7131M2160 Rev B Released 2020-06

Overview

The Sensor IQ DALI Control Option Card (IQ-DALI) controls 24 loops of 64 DALI compatible fluorescent 
ballasts in broadcast mode. This document details the installation of this card in the Sensor IQ Intelligent 
Breaker Panel. Information on installing option cards in other ETC panels is available at 

etcconnect.com

.

Installation

The DALI Control Option Card can be installed on either interior wall of the low voltage 

cavity.

1:

There are four plastic standoffs included with the option card kit. Align the standoffs with the 
mounting holes on the option card so the fins are located opposite the connectors. 

2:

Press gently until the plastic tabs pass through the mounting hole, locking into place.

3:

Align the standoffs with the mounting holes on the interior of the low voltage cavity. 

4:

Press gently until the plastic tabs pass through the mounting hole, locking the option card into place.

Connect Wiring

• The Sensor IQ DALI Control Option Card provides four bus connections for termination of up to 

24 DALI loops total.

• A screw connector is provided for each bus, and is labeled for ease of identification of each output. 
• Each terminal accepts 4–0.25 mm

(12–24 AWG) Class 2 or Class 1 wire. See the white paper 

Understanding 0-10V LED Drivers

 for Class 2 and Class 1 wiring considerations.

Note:

It is best to install any panel option kits after conduit rough-in and load wiring terminations are 
complete to reduce the likelihood of damage to the option card. Reference the 

Sensor IQ 

Installation Manual

Note:

Control wiring must be routed in separate conduit from the line voltage wiring for DALI 

ballasts.

Standoff

 Mounting 
hole

DALI Control 
Option Card

Install option card on 
either interior wall.

Fins

Отзывы: