Step 1: Open the I/O access door to reveal the access points for removable media (USB and SD) and the Status and
LON LEDs.
Step 2: Insert removable media into the appropriate port.
Step 3: Press the “Mode” pin to initiate the “Setup” menu.
Step 4: Press the [Setup] button located on the top left corner of the display.
Step 5: Press [Files] button. A keypad displays for passcode entry.
Step 6: Enter passcode 4116 to access the Files menu.
NOTE: Standard ETC provided themes used in your configuration do not need to be manually uploaded to
the LCD. These themes are loaded for you at the factory and will display beneath the “Themes”
directory.
Step 7: Press the [Config] button to load the configuration file(s) to the Touchscreen or press [Theme] to load the theme
file(s) to the Touchscreen.
Step 8: Press [Load From] and choose the removable media source the configuration files will be loaded from, then
press [OK].
Step 9: Select the specific file (or select multiple files) from the list that you would like to load onto the Touchscreen.
NOTE: It is possible to retrieve configuration files from the Paradigm ACP on the Touchscreen, however
ETC recommends using removable media to load configurations and themes on portable
Touchscreens to reduce commissioning time. If an automatic configuration file transfer begins,
press the [Cancel] button to stop the transfer and manually upload the configuration.
I/O Indicators
•
Reset
pin - when pressed, resets the Portable LCD software
•
Mode
pin - press once for Setup menu. Press and hold for 4 seconds to calibrate the Touchscreen.
•
Aux
LED - indicates the Touchscreen is powered (Aux 24 Vdc)
•
Act
LED - application activity is detected
•
Svc
pin- when pressed, sends the stations Neuron ID to the connected processor
•
Svc
LED- service pin indicator
•
Data
LED - indicates LON network activity
Bind the Portable Touchscreen
Before binding your Portable Touchscreen, please confirm the installation meets the following requirements:
• Both the receptacle station (UH1RS) and the Portable Touchscreen (P-LCD-P) have been added to the configured
space in LightDesigner.
• The Portable Touchscreen must be enabled for use with the specific receptacle station (UH1RS). This is set in the
“Portable” property of the LightDesigner Property Editor for the Touchscreen. You can enable a Portable Touchscreen
to more than one receptacle station in a configuration. The displayed configuration and theme may be different for
each configured Touchscreen and receptacle station connector depending on the assignments in the configured
space.
• The receptacle station’s physical ID (found on a label on the front of the UH1RS station) must be associated to the
configured receptacle station in LightDesigner. This ID should be manually entered into the “Connector ROM” property
in the LightDesigner Property Editor for that station. This is the recommended approach as it avoids manual binding at
the Paradigm processor.
• The LightDesigner configuration has been uploaded to the Paradigm ACP(s). Reference the LightDesigner online help
system for details on uploading a configuration.
Step 1: Physically connect the Portable Touchscreen to the receptacle station (UH1RS).
NOTE: Startup takes a minimum of 20 seconds depending on the configuration. If the receptacle station‘s
physical ID is associated in the Paradigm configuration, the Portable LCD will automatically bind
at startup. If you receive a “No Response from Server” message, proceed to Step 2.
Step 2: At the Paradigm processor facepanel, press enter to access the menu.
Step 3: Navigate to the Arch Setup > LonWorks Connections menu and bind the Touchscreen station using the
“
Connect Device
” option. Reference the Paradigm ACP Configuration Manual for complete details on
connecting a device.
Configuration and Theme Files
Exporting Files from LightDesigner
Step 1: From the LightDesigner configuration, select (File) “Export Portable LCD Files”. The “Export Portable LCD
Files” dialog displays.
Step 2: Select which Portable LCD files will be exported from the selection and click [OK]. The “Browse For Folder”
dialog displays for selection of a location the files will be exported to, such as a removable USB device. Two file
types will be exported, the configuration file saves with a “.lcdconf” extension and the theme saves with an
“.lcdtheme” extension.
NOTE: It is best to store the configuration and theme files to removable media for loading to the
Touchscreen.
Loading Files onto the Touchscreen
NOTE: If the Portable Touchscreen is already bound to the Paradigm processor, it will automatically begin
retrieving its LCD configuration file when powered. Press the [Cancel] button to stop the transfer
and manually load the configuration files instead.