Echoflex Installation Guide

Cubicle Occupancy Sensor

Installation

The ERUSB-C is powered through a USB port.

1. Plug the mini-B end of the USB cable into the ERUSB-C and the other

end into a computer USB port or wall plug adapter.

2. Use double-sided tape or Velcro to mount the ERUSB-C to the wall, if

required. Position the ERUSB-C facing the work station or underneath
the desk where the occupant’s legs rest.

Link to a Controller

The compatible target controller must be installed, powered, and within
range of the ERUSB-C. Both the occupancy sensor and the manual switch
must be linked separately using the following two processes.

Note:

The linking process can be used both to link a device to a

controller and to unlink a linked device from a controller.

To link the occupancy sensor:

1. Press the

[Learn]

button on the controller to activate Link mode. If

necessary, refer to the related product documentation.

2. Press and hold the button on the ERUSB-C for five seconds.
3. Deactivate Link mode on the controller.

To link the manual switch:

1. Press the

[Learn]

button on the controller to activate Link mode. If

necessary, refer to the related product documentation.

2. Press the button on the ERUSB-C once and then press and hold the

button for five seconds.

3. Deactivate Link mode on the controller.

Note:

To use the manual override, you may have to press the

button more than once as the ERUSB-C does not track the relay
state.