ETC Installation Guide

Contact and Demand Response Interfaces

Set Configuration Mode

The configuration mode switch allows selection between Basic and Custom
configurations of the interface. Basic is the factory default setting.

Basic

Basic configuration mode applies the following default behaviors:

Input Interface:

Inputs control Presets 1-4 respectively, using momentary input mode where
the closure behaves similar to an Echo Inspire station.

close / open event (push) executes a preset toggle

holding the contact closed (hold) performs a space raise

closing the closure twice (in rapid succession) performs a preset toggle
with 1/2 second override timing

Note:

Use EchoAccess to assign a different Preset for the contact.

Note:

Particularly when considering machine driven applications,

ETC recommends a minimum of 500 ms between any input changes
to ensure transitions are reliably applied.

Demand Response Interface:

Activates Demand Response, affecting up four consecutive Echo Spaces,
starting with the interface Space rotary switch setting.

Example:

Example: Setting the Space switch to 3 results in control

of Spaces 3, 4, 5, and 6. A value higher than 13 will result in control
of only Spaces 14, 15, and 16.

Note:

Each Echo space can only have one assigned demand response

input.

Functionality:

a closed contact means the designated space is in active Demand
Response state

an open contact means Demand Response is inactive

Output Interface:

Relay outputs are controlled by Zones 1-4 respectively (when the Zone dial is
set to its default setting of 1). Changing the Zone dial will alter the starting
Zone. Reference the related note on

page 7

regarding zone ranges.

Contact and Demand Response Interfaces

Page 5 of 8

ETC

Содержание Echo Contact Input

Страница 1: ...actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface provides four normally open...

Страница 2: ...of wires data and data for both data and power ETC recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not...

Страница 3: ...O normally closed N C and common COM for connection of output relays Terminals accept 0 2 mm 2 4 mm 2 24 12 AWG wire Each output includes a corresponding on board LED to indicate the normally open sta...

Страница 4: ...Wet Contact Input For a wet contact input into the Contact Input Interface you must terminate to both the In and the negative terminal of the 24 VDC auxiliary input The V out terminal will not be use...

Страница 5: ...achine driven applications ETC recommends a minimum of 500 ms between any input changes to ensure transitions are reliably applied Demand Response Interface Activates Demand Response affecting up four...

Страница 6: ...owing default behaviors until changed using the EchoAccess App Input Interface Inputs control Presets 1 4 respectively using maintained input mode where closing the contact activates the preset openin...

Страница 7: ...spaces that will be controlled A value higher than 13 will result in control of only Spaces 14 15 and 16 2 Set the Address Zone For a Contact Input Interface set the Address 1 through 16 available whi...

Страница 8: ...cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset button for ten seconds to reset the interface to factory defaults The power...

Отзывы: