Overview

The Emergency Bypass Detection Kit Reset Switch (EBDK-SWITCH) maintains 
bypass/emergency mode generated by the connected emergency bypass 
detection kit until normal power is restored and a user manually resets the 
system.

Up to two switches may be wired in series per EBDK system. Typical installations 
require a local switch near the dimming system and optionally a second switch in 
the affected lighted area. Only one switch may be wired to a Master Phase Loss 
Detector 2 (MPLD2) device. 

Installation

The EBDK Reset Switch may be installed into an industry standard single-gang back box (provided by 
others) or a single-gang surface-mount back box (sold separately and available by ETC).

The EBDK Reset Switch connects to the emergency bypass detection kit (EBDK) Ext. Switch Input 
connection or to the MPLD2 Remote Restore Switch connection using two 1.5 mm

2

 (16 AWG) wires. 

WAGO cage clamp terminal blocks (two are supplied) are used to connect the EBDK Reset Switch wiring 
harness to the 1.5 mm

2

 (16 AWG) installed control wire.

Note:

You must connect the remote switch (or switches) using the proper polarity. If the 

switch connections are backwards, the EBDK Reset Switch will not operate properly. 

ETC recommends pulling wires of differing color to mitigate complications. The switch 

connections are labeled as follows:
• EBDK: Ext. Switch connection provides two input terminations, V out and Input.
• MPLD2: Remote Restore Switch connection provides two input terminations, 

Out and RTN.

DRd12

rack with

EBDK-TAP

DRd12

rack

120 VAC 3Ø

Normal Power

120 VAC 3Ø

Normal/Emergency Power 

Sense feed

from EBDK-TAP kit

Panic (NO and Common)

EBDK

(2) 1.5 mm

2

(16 AWG)