Echoflex Installation Guide

Dual Tech Occupancy Sensor

Power Up

All EchoConnect terminations in the system must be made before applying
power to the system and sensor. When the sensor is powered up, the PIR and
acoustic detection LEDs illuminate for one minute for calibration and warm-
up. Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance tripping.
During this time configuration is not allowed and no events are triggered.

Configuration

Basic

MODE button

and LED

AUXILIARY 

button 

and LED

A sensor that is set for Basic
configuration mode (DIP switch
2 set to Off) can be further
configured locally using the
other available DIP switch
settings, and the [MODE] and
Auxiliary [A] buttons and their
associated LEDs. See

Preset on

the facing page

.

Custom

A sensor that is set for Custom configuration mode (DIP switch 2 set to On)
can be customized using the ElahoAccess App.

For more detailed information about custom configuration options available
using ElahoAccess, see the ElahoAccess App integrated help system.

Dual Tech Occupancy Sensor

Page 8 of 12

Echoflex

Содержание E-DOC-C-HC

Страница 1: ...ens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m 2 Coverage ft 2 E DOC C SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7 m 800 ft 2...

Страница 2: ...environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sens...

Страница 3: ...ck box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for groundi...

Страница 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Страница 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Страница 7: ...t to On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Swit...

Страница 8: ...ot allowed and no events are triggered Configuration Basic MODE button and LED AUXILIARY button and LED A sensor that is set for Basic configuration mode DIP switch 2 set to Off can be further configu...

Страница 9: ...the preset used 3 Press and release the MODE button to save the current setting Operation Dual Technology When both PIR and acoustic detection are used the following logic is used When the space is va...

Страница 10: ...riod The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or restore the previous lighting condition Aut...

Страница 11: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Отзывы: