Echoflex Installation Guide

Dual Tech Occupancy Sensor

Preset

While in Basic configuration mode (DIP switch 2 set to Off), use the [MODE]
and Auxiliary [A] buttons to program the preset that is activated with an
occupancy detected state change. By default, this is Preset 1. When vacancy is
detected, the default action event is Off.

Follow these steps to configure the preset for your sensor:

1. Access the sensor electronics and press and hold the [MODE] button

for three seconds to enter “Program Mode.” The Mode LED lights in
amber to indicate the sensor is in Program Mode and the Auxiliary LED
flashes to indicate the preset number controlled by the occupancy
action. By default, this is Preset 1, therefore the LED will flash one time,
pause two seconds and flash again.

2. Press and release the Auxiliary [A] button the number of times that

corresponds to the preset that you want to use. For example, press the
[A] button eight times to set Preset 8. The LED flashes the number of
the preset used.

3. Press and release the [MODE] button to save the current setting.

Operation

Dual Technology

When both PIR and acoustic detection are used, the following logic is used:

When the space is vacant, PIR detection and manual control can switch
the state to occupied.

When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.

When occupancy in the space has only been triggered by acoustic
detection for 60 minutes, acoustic detection is disabled until the next
PIR detection event.

PIR (only) Detection

When acoustic detection is disabled (DIP switch 6 set to On), the following
logic is used:

When the space is vacant, PIR detection and manual control can switch
the state to occupied.

When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.

Vacancy Timeout

Vacancy timeout is the amount of time the sensor waits to take action after
no movement is detected. By default, vacancy timeout is set to 15 minutes
(indicated by DIP switch 3 set to Off and 4 set to On; see

DIP Switches on

page 7

). When the vacancy timeout ends, the grace period begins.

Dual Tech Occupancy Sensor

Page 9 of 12

Echoflex

Содержание E-DOC-C-HC

Страница 1: ...ens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m 2 Coverage ft 2 E DOC C SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7 m 800 ft 2...

Страница 2: ...environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sens...

Страница 3: ...ck box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for groundi...

Страница 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Страница 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Страница 7: ...t to On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Swit...

Страница 8: ...ot allowed and no events are triggered Configuration Basic MODE button and LED AUXILIARY button and LED A sensor that is set for Basic configuration mode DIP switch 2 set to Off can be further configu...

Страница 9: ...the preset used 3 Press and release the MODE button to save the current setting Operation Dual Technology When both PIR and acoustic detection are used the following logic is used When the space is va...

Страница 10: ...riod The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or restore the previous lighting condition Aut...

Страница 11: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Отзывы: