ETC Installation Guide

DMX Emergency Bypass Controller

DMX Emergency Bypass Controller Installation Guide

Page 3 of 8

ETC

4:

To further secure the box to the wall, use a single screw (also not provided) in either bottom slot (see 
image below).

Route Conduit and Wiring

Four conduit knockouts are provided on each side of the enclosure for installation convenience. Emergency 
or normal/emergency AC power will utilize the two topmost knockouts while the remaining knockouts 
near the bottom of each side will accommodate the Class 2 wiring (DMX and panic input wire).

Note:

Install the DEBC enclosure on a suitable surface, within 1,640 ft (500 m) of the 

Emergency Bypass Detection Kit (EBDK) or suitable triggering device.

Termination type

Specified wire type

AC input (emergency or normal/emergency) 
2 wires (hot, neutral)

24–10AWG / .2mm

2

–4mm

2

Ground

Ground lug accepts 14–2AWG / 2.5mm

2

–35mm

2

Panic input

30–12AWG / .05mm

2

–2.5mm

2

DMX in/out

Belden 9729 (or approved equivalent for DMX, such as 
CAT5 or CAT5E with insulation displacement 
connectors)

Note:

Power and control wires must be run in separate conduits. Follow all local code 

restrictions.

1 in

(25.4 mm)

6.5 in

(165 mm)

2.5 in

(63 mm)

10 in

(254 mm)

11 in

(280 mm)

9 in

(229 mm)

Secure with a 

screw in either 

bottom slot

Содержание DMX DEBC-1

Страница 1: ...e ETC Emergency Bypass Detection Kit EBDK or other suitable power sensing device The DEBC may also operate as part of a closed loop fire alarm system The DEBC requires that the electrical supply to th...

Страница 2: ...r jeweler s screwdriver for wire terminations 2 Phillips screwdriver for the front cover Four mounting bolts or screws suitable to hold up to 6 lb 2 7 kg Install the DEBC 1 Remove the front cover from...

Страница 3: ...lass 2 wiring DMX and panic input wire Note Install the DEBC enclosure on a suitable surface within 1 640 ft 500 m of the Emergency Bypass Detection Kit EBDK or suitable triggering device Termination...

Страница 4: ...the screw firmly onto the wire 5 Insert the second panic input wire into the INPUT terminal Using the jeweler s screwdriver tighten the screw firmly onto the wire 12VDC Signal 1 Strip 1 4 6 mm insulat...

Страница 5: ...s follows Single output DEBC DMX OUT THRU to J9 see image at right Six output DEBC DMX OUT THRU to J9 and DMX OUT to J10 J11 J5 J6 and J7 see image below Note A DMX Cable Preparation Kit with Screw Co...

Страница 6: ...sert it into pin 1 labeled L on the AC INPUT terminal tighten the terminal firmly onto the wire 6 Locate the neutral wire typically white and insert it into pin 2 labeled N on the AC INPUT terminal ti...

Страница 7: ...button and the Normal Bypass indicator while replacing the cover 3 Restore power to the main breaker that supplies power to the controller See Operational Notes and Testing for details of how the DMX...

Страница 8: ...l DMX source is outputting DMX to the normal emergency lighting fixtures through the DEBC 3 Hold down the RECORD button located at S2 on the control board for approximately 5 seconds The Status LED lo...

Отзывы: