ETC Installation Guide
DMX Emergency Bypass Controller
DMX Emergency Bypass Controller Installation Guide
Page 3 of 8
ETC
4:
To further secure the box to the wall, use a single screw (also not provided) in either bottom slot (see
image below).
Route Conduit and Wiring
Four conduit knockouts are provided on each side of the enclosure for installation convenience. Emergency
or normal/emergency AC power will utilize the two topmost knockouts while the remaining knockouts
near the bottom of each side will accommodate the Class 2 wiring (DMX and panic input wire).
Note:
Install the DEBC enclosure on a suitable surface, within 1,640 ft (500 m) of the
Emergency Bypass Detection Kit (EBDK) or suitable triggering device.
Termination type
Specified wire type
AC input (emergency or normal/emergency)
2 wires (hot, neutral)
24–10AWG / .2mm
2
–4mm
2
Ground
Ground lug accepts 14–2AWG / 2.5mm
2
–35mm
2
Panic input
30–12AWG / .05mm
2
–2.5mm
2
DMX in/out
Belden 9729 (or approved equivalent for DMX, such as
CAT5 or CAT5E with insulation displacement
connectors)
Note:
Power and control wires must be run in separate conduits. Follow all local code
restrictions.
1 in
(25.4 mm)
6.5 in
(165 mm)
2.5 in
(63 mm)
10 in
(254 mm)
11 in
(280 mm)
9 in
(229 mm)
Secure with a
screw in either
bottom slot