ETC Installation Guide
SC1008 BCELTS
SC1008 BCELTS
Page 9 of 11
ETC
Final Installation and Power Up
1. Check that each termination point is secure.
2. Check that the fire alarm contact input switches
are set for correct switch operation, either
normally open or normally closed.
3. Clear all debris from the inside of the enclosure.
4. Remove and discard the orange plastic strip that is
securing the relays in place.
5. Attach and secure the front cover to the enclosure.
6. Apply both normal and emergency power to the
unit.
7. Test the operation of the SC1008 as described in
below.
Operation and Test
It is important to test the SC1008 regularly because it is a life safety device. NFPA 101 Life Safety
code requires testing of life safety devices every 30 days.
Test the SC1008 unit using either the test button or laser test as described in the following sections.
LED States
Red
LED
Green
LED
State
Notes
On
On
Normal and emergency power
are both present. The SC1008 is
supplying Normal power to the
load.
Blinking
Off
The SC1008 is supplying
emergency power to the load.
This may be due to the loss of normal
power, the making of the fire alarm
contact, or the activation of the test
mode.
Off
On
Normal power is present;
emergency power is not.
The SC1008 is supplying normal power to
the load and will not transfer.
Off
Off
Neither normal nor emergency
power are being supplied to the
unit.
If the LEDs are not lit as expected when
power is present, it is possible that one or
both of the internal fuses have blown. See
to check
and replace the fuses.
Blinking
Blinking
Relays are detected in an invalid
state
If both LEDs are blinking, the SC1008
relays need to be manually reset to a
known state. See
for detailed instructions.