25
DELAY
In main menu choose “PARAM” (fig.2) and press “E” key. Display shows:
DEL.: ->00
0 0 0 0
fig.9
The -> arrow is on “DEL”. This value is pump’s waiting time after any start up procedure: pump will wait set time before
start dosing every time it is powered on. Use “UP” and “DOWN” keys to change this value. Waiting time may be set from
1 to 60 minutes.
pASSWORD
In main menu choose “PARAM” (fig.2) and press “E” key. Display shows:
DEL.: ->00
0 0 0 0
fig.9
Press “RIGHT” key to move on 0 0 0 0. All new pumps have “0 0 0 0” as default password, use “UP” and “DOWN” keys
to change this value. Press “E” to confirm new data. The pump shows the new password for about two seconds then it’ll
return to main menu. Press “RIGHT” key to leave main menu.
MAXIMUM TIME DOSING ALARM
This alarm prevents the pump to dose if a set time is reached. To set this alarm enter into “Setup menu” as shown in fig.3.
Use “DOWN” key to choose “3) Alarm” and press “E” key. The pump shows:
-> AL OFF
DOSING
fig.10
To activate the alarm use “UP” or “DOWN” keys to set the time (from 1 to 100 minutes or “AL OFF”). To setup the alarm
mode use the “RIGHT” key. Cursor moves on “DOSING”. Use “UP” or “DOWN” keys to change this voice. On “STOP” mode
the pump will stop the dosing procedure once the set time is reached. The pump’s display will show the alarm condition
and requires to press a key to continue. On “DOSING” mode the pump will NOT stop the dosing procedure once the set
time is reached. The pump’s display will show the alarm condition and requires to press a key to continue.
Special functions
- Keep pressed the “UP” key to turn off the pump. Display shows “OFF” and it will switch off. Keeping pressed the “UP”
key the pump will switch on.
- Keep pressed the “DOWN” key to read on display the power supply input.
- Keep pressed the “E” key for manual dosing.
- Pump’s reset: turn off the pump, keep pressed “UP” and “DOWN” keys then turn on the pump. Release “UP” and “DOWN”
keys and proceed to pump’s set-up. This procedure will return the pump to its shipment condition.
Содержание AMS DIGITAL
Страница 34: ...37 H...