Error Messages
ET System electronic GmbH
19
ERROR MESSAGES
The following table shows solutions for common error messages in case of disorder.
Error
Description
Possible Cause
Solution
Err-01
U-Phase IGBT1 overcurrent fault
IGBT Phase U is damaged
Check and replace IGBT
Err-02
U-Phase IGBT2 overcurrent fault
IGBT Phase U is damaged
Check and replace IGBT
Err-03
U-Phase IGBT3 overcurrent fault
IGBT Phase U is damaged
Check and replace IGBT
Err-04
U-Phase IGBT4 overcurrent fault
IGBT Phase U is damaged
Check and replace IGBT
Err-05
V-Phase IGBT1 overcurrent fault
IGBT Phase V is damaged
Check and replace IGBT
Err-06
V-Phase IGBT2 overcurrent fault
IGBT Phase V is damaged
Check and replace IGBT
Err-07
V-Phase IGBT3 overcurrent fault
IGBT Phase V is damaged
Check and replace IGBT
Err-08
V-Phase IGBT4 overcurrent fault
IGBT Phase V is damaged
Check and replace IGBT
Err-09
Overcurrent fault W-Phase IGBT1
IGBT Phase V is damaged
Check and replace IGBT
Err-10
Overcurrent fault W-Phase IGBT2
IGBT Phase V is damaged
Check and replace IGBT
Err-11
Overcurrent fault W-Phase IGBT3
IGBT Phase W is damaged
Check and replace IGBT
Err-12
Overcurrent fault W-Phase IGBT4
IGBT Phase W is damaged
Check and replace IGBT
Err-13
Radiator over-temperature
Fan malfunction
Check fan
Err-14
Transformer over-temperature
Fan malfunction
Check fan
Err-15
Emergency stop button
Emergency stop button is pushed
Check emergency stop button
Err-16
Fuse 1 is defect
Fuse 1 is damaged
Check and replace fuse
Err-17
Fuse 2 is defect
Fuse 2 is damaged
Check and replace fuse
Err-18
Fuse 3 is defect
Fuse 3 is damaged
Check and replace fuse
Err-19
IGBT over-temperature 1
Fan malfunction
Check fan
Err-20
IGBT over-temperature 2
Fan malfunction
Check fan
Err-21
Input undervoltage error
Input voltage is too low
Check input voltage
Err-22
Input overvoltage error
Output voltage is too high
Check input voltage
Err-23
DC-Spannung zu gering
Input voltage is too low
Check input voltage
Err-24
DC-Spannung zu hoch
Output voltage is too high
Check input voltage
Err-25
Overload U
U phase overload
Check load
Err-26
Overload V
V phase overload
Check load
Err-27
Overload W
W phase overload
Check load
Err-28
Output undervoltage error
Output voltage too low
Check output voltage
Err-29
Output overvoltage error
Output voltage too high
Check output voltage
MAINTENANCE
The fan should be examined for its functionality and cleaned from contamination at regular intervals. For this purpose,
the ventilation duct must be removed and the fan can easily be taken out.