background image

www.esylux.com

2 13

/

PRESENCE DETECTOR      PD-C360i/24 KNX ECO      (EP10425844)

GB

DESCRIPTION OF COMMUNICATION OBJECTS

INPUTS

Object Ø:

Input light lock

The output light (Object 5) is locked by an ON telegram.

This is unlocked with an OFF telegram.

Options for a change in state after input lock:

- No change
- Switch off
- Switch on

Object 1

Input light

Switches between the orientation light values (with constant light control feature)

An ON telegram changes the setting from orientation light value 1 to orientation light value 2.

An OFF telegram changes the setting from value 2 to value 1.

Object 2

Input light, on/off manually

  Essential when in half automatic mode!

Object 3

Input light, dim manually

*Feature: Constant light control

Input for KNX touch sensors

Dim up, dim down

Содержание PD-C360i/24 KNX ECO

Страница 1: ...owledged 3 x with the red LED In the Slave function each detection is acknowledged 2 x with the green LED NOTE The green LED will only light up when motion is detected if it has been enabled by the ET...

Страница 2: ...ck No change Switch off Switch on Object 1 Input light Switches between the orientation light values with constant light control feature An ON telegram changes the setting from orientation light value...

Страница 3: ...PUTS Object 5 Output light on off Feature Switching Constant light control If persons are present and artificial lighting is required the output sends an ON telegram If natural light is sufficient and...

Страница 4: ...are present an OFF telegram is sent once the switch off delay time has elapsed Optional offset dim value 2 to dim value 1 50 to 50 Object 9 Output light value The output light value transmits every 1...

Страница 5: ...two Masters can work in parallel Each Master evaluates the presence Object 13 and 14 according to its parameters set via the ETS Engineering Tool Software and controls the lighting appropriately Defa...

Страница 6: ...lt setting ON 4 SWITCH OFF TIME PRESENCE OUTPUT HVAC Option of selecting a switch off time delay of 0 sec 10 sec or 1 min 60 min NOTE The presence output is independent of the set light values Default...

Страница 7: ...be smaller than the light value on the work surface below The difference varies greatly and is dependent on local conditions Dark surfaces cause a low level of reflection Light matte surfaces cause a...

Страница 8: ...an be switched on or off manually at any time using infrared remote control Mobil PDi User please also refer to separate Mobil PDi User instructions or by telegrams e g by pressing external KNX EIB bu...

Страница 9: ...switch off delay time has elapsed The lighting can subsequently be switched back on manually at any time If the artificial light has been switched on manually due to low ambient brightness conditions...

Страница 10: ...ght control Default setting Switching 12 THRESHOLD SWITCHING Options 0 disabled Options 1 lux 2000 lux up down menu or direct entry 0 lux 2000 lux Default setting 500 lux There is an option of determi...

Страница 11: ...n Default setting 5 min 15 CONSTANT LIGHT CONTROL Control timing Options 0 5 sec 10 sec up down menu NOTE If the control loop exhibits a hunting tendency the sensor can be adjusted to various illumina...

Страница 12: ...rol NOTE The orientation light value 1 is active as standard Via Object 1 an ON telegram changes the setting to orientation light value 2 and an OFF telegram changes the setting to orientation light v...

Страница 13: ...ways on if the light falls below the set value 1 min 250 min up down menu or as direct entry 0 min 250 min applies to both orientation light values NOTE Only active for constant light control NOTE Onl...

Отзывы: