Initial operation
5.
Initial operation
5.1 Warm-up phase
The motion detector initiates a warm-up phase each time the mains
voltage is connected.
¾
Connect the mains voltage.
9
A warm-up phase of approx. 45 seconds is initiated.
9
During this time, the lighting is switched on.
9
When the motion detector is commissioned for the first time,
the detector LED flashes blue – red – red alternately.
9
The warm-up phase is over when the green detector LED briefly
flashes three times after this and the lighting switches off again.
If individual settings have already been configured on the motion
detector, the detector LED flashes blue – red alternately during
the warm-up phase.
5.2 Default settings
The motion detector is equipped with default settings. It is ready for
operation after the warm-up phase and operates in accordance with the
default settings.
Default settings:
MD 200°
Operating mode
Fully automatic
Brightness switching value
20 lx
Switch-off delay time
5 min.
Motion sensor sensitivity
100 %
Detector LED
On
Test mode
Off
Warm-up phase