Operation manual for M RS 420 ESTYMA control unit 

18

 

  

AMOUNT OF AIR, LAMBDA SENSOR – POWER TEST MODE 

 

The combustion process requires the supply of air, the amount of which depends 
on  the  type  of  fuel  and  the  power  of  the  heating  unit.  Therefore,  the  optimal 
amount  of  air  should  be  set  for  each  type  of  fuel  and  each  burner  power  level. 
This should be done by the person who starts up the control unit. The parameters 
are saved in the non-volatile memory of the control unit. 

In order to set the optimal amount of air, one should: 

- set the type of fuel corresponding to the fuel to be used, 

- turn on the control unit, 

- enter the POWER TEST submenu and run the “power test mode”. 

- set the amount of air for 20, 40, 60, 80, 100% of the burner power. The values 
will be calculated by approximation method from the selected curves. See Figure 
11.  

If the control system includes the optional Lambda module, oxygen values should 
be  set  in  a  similar  fashion  for  the  various  burner  power  levels.  The  parameters 
should be set in line with the boiler manufacturer’s specifications, or on the basis 
of the results of waste gas analysis at the different burner power levels.  

If  the  blower power  is  controlled  using the  optional  Lambda  sensor  module, the 
blower  power  may  be  adjusted  within  the  range  of  ±10  adjustment  units.  This 
relationship is shown in Figure 12. 

NOTE!!! 

Turn  off  the  chimney  sweep  mode  once  you  have  completed  the 

adjustments. 

When  adjustments  are  made  in  the  power  test  mode,  automatic  burner  power 
control  is  deactivated  so  as  to  allow  measurements  and  analyses  at  constant 
burner power. 

 

Содержание Control M RS 420

Страница 1: ......

Страница 2: ...IGATION 10 BOILER OPERATION MODES 12 WEATHER COMPENSATED MODE WITH MIXER ACTUATOR CONTROL 12 MANUAL MODE 12 SUMMER MODE 13 BOILER TEMPERATURE SETTING 13 CONTROL OF THE FOUR WAY MIXING VALVE 14 HEATING...

Страница 3: ...of the air supplied to the combustion process Thanks to solid state relays SSRs the blower has variable speed control and the reliability of the unit controlling the feeder motor has been greatly incr...

Страница 4: ...between the unit and the user and the interface is very easy to use A new intuitive menu in several languages Polish English German French Lithuanian Russian A Lambda sensor ensures optimum supply of...

Страница 5: ...Operation manual for M RS 420 ESTYMA control unit 5 Figure 1 Flowchart of the control unit operation...

Страница 6: ...this may cause short circuiting electric shock fire or damage to the unit Do not allow water humidity or dust to enter the unit as this may cause short circuiting electric shock fire or damage to the...

Страница 7: ...lead must be replaced by a maintenance service provider with a new one having the same parameters as the original lead DISPOSAL OF OLD EQUIPMENT This electronic equipment is made of materials which ar...

Страница 8: ...cal connections LOCATION The unit is intended for indoor installation only After selecting the location make sure that it meets the following requirements The location must be free from excessive humi...

Страница 9: ...ee the contact details on the last page of this manual ROOM TEMPEATURE REGULATOR The M RS ESTYMA controller can work with any temperature room regulator with closing contacts The room regulator should...

Страница 10: ...is shown in Figure 2 submenus are used to display and change operation parameters In order to change a parameter press ENTER The parameter changed is displayed in cycles In order to edit the parameter...

Страница 11: ...Operation manual for M RS 420 ESTYMA control unit 11 Figure 4 MENU...

Страница 12: ...rogrammable heating curve so there is no need to change the boiler temperature manually when the outdoor temperature changes As a rule nights are colder than days The boiler temperature is a function...

Страница 13: ...MODE This mode of the controller is used in summer to heat water In this mode the central heating circulation pump is not turned on unless there is an alarm signal The boiler temperature is set manual...

Страница 14: ...temperature of the returning medium is exceeded the element responsible for maintaining the required temperature downstream from the mixer takes over control The temperatures are set in the HEATING s...

Страница 15: ...ine with the adjustment guidelines included in Table No 1 Adjustment guidelines PROBLEM ADJUSTMENT Room temperature is too low within the whole range of outdoor temperatures Increase the curve offset...

Страница 16: ...or M RS 420 ESTYMA control unit 16 SYMBOL INSTALLATION TYPE A Floor heating system B Low temperature heating system C Heating system with temperature exceeding 75 C Table 2 Heating system types Figure...

Страница 17: ...Operation manual for M RS 420 ESTYMA control unit 17 Figure 8 Heating curve offset Figure 9 Modification of heating curve slope...

Страница 18: ...air for 20 40 60 80 100 of the burner power The values will be calculated by approximation method from the selected curves See Figure 11 If the control system includes the optional Lambda module oxyge...

Страница 19: ...Operation manual for M RS 420 ESTYMA control unit 19 Figure 10 POWER TEST submenu Figure 11 Blower power curve Figure 12 Blower power curve with Lambda based control...

Страница 20: ...MODE submenu The hot water pump runs only when the temperature of the heating medium in the boiler is higher than the water temperature in the hot tap water tank In this way losses of energy stored in...

Страница 21: ...default setting if the hot water pump runs for more than 20 min default setting and the set hot tap water temperature is not attained The relevant SERVICE MODE submenu parameters are stop HP hwp and...

Страница 22: ...eeder are controlled manually ON the control unit is on NOTE When OFF is displayed on the screen the control unit is actually in a standby mode and is energized in case of an alarm the control unit wi...

Страница 23: ...ess to turn the feeder on off Press to turn suction on off After you press the button the feeder will run for 30 seconds filling the retort with fuel about half way Once this happens turn the boiler c...

Страница 24: ...unit s memory no flame no fuel the alarm is activated when there is no fuel or no flame in the burner check suction system the alarm is activated if the suction system has made three consecutive fail...

Страница 25: ...r pump 100W Lighter 400W Blower 150W Feeder motor 200W Automatic exchanger cleaning suction motor 100W Mixer actuator 50W Boiler temp setting range 60 85 C Hot tap water setting range 35 70 C Temperat...

Страница 26: ...Operation manual for M RS 420 ESTYMA control unit 26 estyma electronics Gajewo Al Lipowa 4 11 500 Gi ycko POLAND phone 48 87 429 86 75 fax 48 87 429 86 75 biuro estyma pl www estyma pl...

Отзывы: