To install the detector: 

1.  Install and wire the base, as described on the installation 

sheet supplied with the base. 

2.  Remove the serial number label from the detector and 

attach it to the project documentation. 

3.  Attach the detector to the base by rotating the detector 

clockwise until it snaps into the locked position. 

Testing

Before testing, notify the proper authorities that the fire alarm 

system is undergoing maintenance and will be temporarily out 

of service. 

Caution: 

Heat damage. Excessive heat may damage the 

detector outer cover. Do not apply excessive heat when using 

a hair dryer. When using a Testifire detector tester, you must 

install a SIGA2 Testifire Adapter Assembly. 

Make sure the SIGA2 Testifire Adapter Assembly (model 

SIGA2-TSTSPACER) is installed in the Testifire detector tester 

before testing. Refer to the 

SIGA2 Testifire Adapter Assembly 

Installation Sheet

 (P/N 3101942) for further details. 

To perform an initial installation test: 

1.  Visually inspect each detector and verify that it is installed 

in the correct location. Make sure it is not adversely 

affected by factors not apparent on the plans. 

2.  Remove the detector from its base and verify that the 

proper detector address, trouble signals, and messages 

are reported. 

3.  If wired for Class A operation, verify that the detector 

continues to operate first with the SLC_IN disconnected, 

and then with the SLC_OUT disconnected. (Refer to the 

installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC circuit to 

verify operation of the ground fault detection circuitry. 

5.  Perform a sensor function test, as described below. 

To perform a function test:  

1.  If desired, use the fire alarm control panel to put the 

detector or zone into a service group for testing. (Refer to 

the panel technical reference manual for instructions.) 

2.  Activate the heat sensor using a hair dryer (maintaining a 

distance of three inches) or using a Testifire detector 

tester per the manufacturer’s instructions. 

Maintenance

To ensure proper operation, plan maintenance in accordance 

with the requirements of the authority having jurisdiction. Refer 

to CAN/ULC-S536 

Standard for the Inspection and Testing of 

Fire Alarm Systems

 and NFPA 

72 National Fire Alarm and 

Signaling Code.

 

Refer to Technical Bulletin P/N 270145 REV 4.0 or later for 

additional information and cleaning instructions. 

Specifications

 
Operating voltage 

15.20 to 19.95 VDC 

Current 

 

Normal operating 

 

Alarm 

 

Stand-alone alarm 

 

45 µA 

45 µA 

18.4 mA 

Rate-of-rise 

15°F/min (8°C/min) 

Maximum spacing [1] 

50 ft. (15.2 m) centers 

Compatible bases 

 

Standard 

 

Relay 

 

Isolator 

 

Audible 

 

SIGA-SB, SIGA-SB4 

SIGA-RB, SIGA-RB4 

SIGA-IB, SIGA-IB4 

SIGA-AB4, SIGA-AB4G 

Compatible detector testers [2]  Testifire 1000, Testifire 2000 
Operating environment 

 

Temperature 

 

Relative humidity 

 

32 to 100°F (0 to 38°C) 

0 to 93% noncondensing  

Storage temperature 

4 to 140°F (

20 to 60°C) 

[1] When replacing SIGA-HRS and SIGA-HFS detectors with the 

SIGA2-HRS, ensure that the spacing is 50 ft. (15.2 m) or less. 
[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly. 

Regulatory information 

 
Manufacturer 

Edwards, A Division of UTC Fire & Security 

Americas Corporation, Inc. 

8985 Town Center Parkway, Bradenton, FL 

34202, USA 

Year of 

manufacture 

The first two digits of the date code (located on 

the product identification label) are the year of 

manufacture. 

North American 

standards 

CAN/ULC-S530-M91, UL 521 

UL/ULC fixed-temp 

alarm rating 

135°F (57.2°C) 

Alarm point 

 

UL 

 

ULC 

 

129 to 144°F (53.9 to 62.2°C) 

129 to 141°F (53.9 to 60.6°C) 

FCC compliance 

This device complies with part 15 of the FCC 

Rules. Operation is subject to the following two 

conditions: (1) This device may not cause harmful 

interference, and (2) this device must accept any 

interference received, including interference that 

may cause undesired operation. 

Industry Canada 

compliance 

This Class A digital apparatus complies with 

Canadian ICES-003. 

Contact information 

2 / 2 

 

For contact information, see www.griyateknik.co.id 