Figure 10: RS-232 wiring for serial printers (TB5)
Legend
(1) Supervised serial
printer (3=RX, 7=Common, 20=DTR)
(2)
Unsupervised serial printer (2=TX, 3=RX, 7=Common)
(3) Front view of male DB-
25 connector
Notes
•
Locate a supervised serial printer in the same room as the equipment to which it connects.
•
Locate an unsupervised serial printer in the same room of the equipment to which it connects, and enclose wiring in conduit or equivalent
protection against mechanical injury.
•
RS
-232 wiring is approved for connection of fire alarm or ancillary equipment; however, both applications cannot be supported on the same
connection or wiring.
Figure 11: RS-232 wiring to ancillary devices
Legend
(1) To the COM terminal on listed equipment
(2)
To the R
xD terminal on listed equipment
(3) To the TxD terminal on listed equipment
Note
:
RS
-232 wiring is approved for connection of fire alarm or
ancillary equipment; however, both applications cannot be supported
on the same connection or wiring.
Figure 12: Smoke power and AUX SLC wiring (TB1/TB2)
Legend
(1)
Smoke power to SIGA
-
UM or SIGA MAB for a two
-wire
smoke detector
(2) External equipment with compatible ratings
Note
:
AUX power wiring used for fire functions cannot be shared with
any device performing ancillary functions.
AUDIO
AUDIO
AUDIO
AUDIO
B IN
B IN
B OUT
B OUT
+
+
-
-
+
+
-
-
A
A
B
B
RS-485
RS-485
+
+
-
-
+
+
-
-
RS-485
RS-485
R
R
X
X
1
1
T
T
X
X
1
1
T
T
S
S
1
1
R
R
O
O
M
M
1
1
C
C
BUS
BUS
BUS
BUS
3
3
2
7
20
7
(3)
(3)
(1)
(2)