EST iO64 Скачать руководство пользователя страница 2

Page 2 of 10

 

  D A T A   S H E E T

 85005-0131

 

Not to be used for installation purposes.

  Issue 7

Operation 

The front panel provides an 
easy-to-use operator’s inter-
face, as well as all the neces-
sary controls for front panel 
programming. A large back-lit 
80-character LCD displays 
system status, event details, 
and programming prompts. 
Large tactile control buttons 
are easy to see in low light 
conditions, and bright multi-
color LEDs offer at-a-glance 
status indication.

Control buttons

Button

Description

System Reset

Initiates a system reset.

ACK/Panel 
Silence

Silences the panel and remote annunciators during 
an active trouble, supervisory, or alarm event and 
acknowledges new event activations.

Signal Silence

Alarm mode:

 Silences active notification appliances. 

Pressing Signal Silence a second time turns NACs back 
on.

Drill

Initiates a drill confirmation. Pressing drill a second time 
turns off the drill function.

Remote 
Disconnect

Dialer:

 Disables or enables dialer. 

Dialer set to modem only:

 Disables or enables the 

common alarm relay.

Left arrow

Display mode:

 Moves the cursor to the left.

Menu mode:

 Toggles between programming 

selections.

Right arrow

Display mode:

 Moves the cursor to the right.

Menu mode: 

Retrieves a programming option’s sub 

menu and toggles between a programming option’s 
selections.

Up arrow

Display mode: 

Advances to the previous event.

Menu mode:

 Moves the cursor up.

Down arrow

Display mode: 

Advances to the next event.

Menu mode: 

Moves the cursor down.

Enter

Display mode: 

Displays selected event details.

Menu mode: 

Retrieves a programming option’s sub 

menu or jumps to the 

Save

 function in the menu.

Entry mode: 

Enters the selected data into the system.

Cancel

Display mode: 

Exits the detailed information display.

Menu mode: 

Exits the current menu level.

Entry mode:

 Clears the current entry.

Menu

Display mode: Enters the menu mode
Menu mode: Exits menu mode

Space

Enters a space, such as a space between words.

Alphanumeric 
keypad

Entry mode:

 Pressing a button once enters the number 

on the button. Pressing the button twice enters the 
secondary value.

Programmable 
buttons

These buttons can be programmed to control outputs, 
disable devices or unlatch system outputs.

Application

The iO64 life safety system is a powerful intelligent solution for small 
to mid-sized buildings. Advanced analog technology delivers the 
benefits of flexible system installation, while a clean and easy-to-
operatate user interface makes panel operation and system mainte-
nance quick and intuitive.

The smart choice

Signature Series electronic addressing eliminates the tedium of 
setting dipswitches, and automatic device mapping ensures that 
each device resides on the system at its correct location. Mean-
while, innovative programming features allow the system designer 
to customize powerful built-in features to precisely suit the needs 
of the building owner.

Flexibility built right in

Two fully-programmable front panel switch/LED combinations pro-
vide an added measure of flexibility. Their slide-in labels take the 
mystery out of custom applications, and present a clean finished 
appearance.

Perfect for retrofits

The iO64 is particularly well-suited to retrofit applications. All 
connections are made over standard wiring – no shielded cable 
required. This means that in most situations existing wiring can be 
used to upgrade a legacy control panel to iO-Series technology 
without the expense or disruption of rewiring the entire building.

Signals with a difference

iO64 NACs are configurable to fully support the advanced signal-
ing technology of Edwards Genesis and Enhanced Integrity notifi-
cation appliances. These devices offer precision synchronization of 
strobes to UL 1971 standards. For Genesis devices, enabling this 
feature allows connected horns to be silenced while strobes on 
the same two-wire circuit continue to flash until the panel is reset.

Clear-cut remote annunciation

Remote annunciation is a strong suit of the iO64. Up to eight an-
nunciators can be installed on a single system. Compatible annun-
ciators include a range of LED and LCD models that provide zone 
or point annunciation, as well as common control capabilities.

The iO64 also supports graphic annunciation with optional graphic 
annunicator interface modules. Each interface provides common 
control, indicators, and LED drivers. Consult the Ordering Informa-
tion section for details.

A complete line of accessories

The iO64 life safety system is supported by a complete line of 
intelligent detectors, modules and related equipment. Consult the 
Ordering Information section for details.

Содержание iO64

Страница 1: ...nd related equip ment including Signature Series intelligent modules detectors and bases R Series remote annunciators option cards that expand system capacity and extend system capabilities fully integrated CO detection using Signature Series 2 detec tors with or w o audible signaling Features Comes standard with one loop that supports up to 64 intelligent devices of any type and two Class B NACs ...

Страница 2: ...plication The iO64 life safety system is a powerful intelligent solution for small to mid sized buildings Advanced analog technology delivers the benefits of flexible system installation while a clean and easy to operatate user interface makes panel operation and system mainte nance quick and intuitive The smart choice Signature Series electronic addressing eliminates the tedium of setting dipswit...

Страница 3: ... walk test Steady indicates a silent test Monitor Yellow LED Flashes when there is an active monitor event on any loop On steady once acknowledged Service Detector Yellow LED Indicates that detector needs servicing Signal Silence Yellow LED On steady indicates that NAC circuits are turned off but the panel is still in alarm Remote Discon nect Yellow LED On steady indicates that the dialer is disab...

Страница 4: ...1 SEC Loop 1 PRI Loop device Loop device Loop card Data Line Class B Wiring Class A Wiring Marking indicates output signal polarity when the circuit is active Polarity reverses when the circuit is not active Wire notification appliances accordingly Notification appliance polarity shown in active state Annunciator loop TB4 The control panel provides a connection for up to eight serially driven and ...

Страница 5: ...32 wiring SA CLA Class A Module The SA CLA card provides Class A capability for NAC loop and an nunciator wiring Its terminal block provides the wiring connection for NAC return wiring The card is required for loop and annuncia tor Class A wiring even though this wiring does not return to the SA CLA card The SA CLA is compatible with iO64 control panels only iO500 panels are Class A ready The SA C...

Страница 6: ...g agents such as CO2 Halon or foam The module is easily configured in the field and of fers a wide range of options that ensure dependable service while preventing the unnecessary release of extinguishing agent SIGA REL specifications Power riser Input voltage Supervisory current Riser input current Alarm 24 Vdc power limited 25 mA max 4 amps maximum 170 mA min 4 A max Release circuits Output rati...

Страница 7: ...e mount enclosure 230 Vac Spanish iO64G PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 115 Vac Portuguese iO64G 2 PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 230 Vac Portuguese iO64GL Note 1 1 Loop System 64 point capacity 2 Class B NACs 16 zone LED display gray door surface mount enclosure 115 Vac English iO64GL F Note 1 1...

Страница 8: ...4 0 15 SIGA MCRR Polarity Reversal Relay Module UIO Mount 0 18 0 08 SIGA RM1 Riser Monitor Module Standard Mount 0 5 0 23 SIGA MRM1 Riser Monitor Module Plug in 0 18 0 08 SIGA IO Input Output Module Standard Mount 0 34 0 15 SIGA MIO Input Output Module Plug in 0 22 0 10 SIGA MAB Universal Class A B Module Plug in 0 18 0 08 SIGA CT1 Single Input Module 0 4 0 15 SIGA CT2 Dual Input Module 0 4 0 15 S...

Страница 9: ... EOL Polarized end of line relay English markings on stainless steel cover 0 2 0 1 SIGA UIO2R Universal Module Board w Riser Inputs Two Module Positions 0 32 0 15 SIGA UIO6R Universal Module Board w Riser Inputs Six Module Positions 0 62 0 28 SIGA UIO6 Universal Module Board Six Module Positions 0 56 0 25 Accessories GCI Graphic Annunciator Driver provides outputs for common indicators and 32 alar...

Страница 10: ... EST is an EDWARDS brand 1016 Corporate Park Drive Mebane NC 27302 In Canada contact Chubb Edwards Email inquiries chubbedwards com Web www chubbedwards com 2013 UTC Fire Security Americas Corporation Inc All rights reserved Specifications subject to change without notice Edwards is part of UTC Climate Controls Security a unit of United Technologies Corporation ...

Отзывы: