Copyright 2003-2013 CSM CO.,LTD
- 16 -
APC-TF Series
Manual with remote control operation
wiring diagrams
•
Manual with remote control mode : Control by external potentio meter set-point
value with “P.W” potentio meter setting up value.
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
⑪
⑫
⑬
⑭
NC COM NO
OPEN : Stop
CLOSE : Running
External
potentiometer : 10KΩ
State
items
The setting up items and explanation
Default
value
External
signal
Not used.
SW3
EXT MODE :External potentio meter select
INT MODE
SW4
MANUAL MODE : Manual operation mode select
The setting up in the case which the utility does an AUTO/MAN switch in the
outside control panel at necessarily select AUTO mode.
AUTO
MODE
SW5
STOP MODE
** Use when the liver diagnoses or power controller test.
If select of “RUN” mode ,the control is impossible to an external of contact.
STOP
MODE
S.S
The time set for soft start, stop, up, down control. (1-10 Sec)
The setting up of soft control value for start time, stop time, up time and
down time so that it is suitable to the characteristic of the load at 1-10 sec.
3 sec
P.W
It uses output voltage, current, conduction angle, phase-shift and power
factor to compute the power.
The adjustment range is 0 to 100% of the units rating.
The case of a guidance inductive load, order the increase adjustment clockwise
slowly from necessarily 0 % to maximum stability range.
100 %
O.C
Over current setting up.
Power controller set in “STOP” situation and set of the load capacity
in 120 – 150% range.
Nominal
current
115%
4 – 20mA
Potentio meter AUTO/MANUAL RUN/STOP Reset Alarm relay