When there is no wind, it consumes the electricity from the battery group. Therefore, after 
discharging, the batteries should be recharged soon, especially for lead-acid batteries. If 
the  batteries  cannot  be  recharged  quickly  after  over  discharging,  the  working  life  of  the 
batteries  will  be  reduced.  The  users  should  regulate  the  consumption  of  electricity 
according to local wind conditions and the output of the wind generator, or have alternative 
charging methods available. 

 
5.1.3  After  passing  full  wave  bridge  rectification,  the  3-phase  AC  electricity  generated  by  the 

wind generator will output in DC24V, 36V, 48V, or 120V DC to charge the battery group. 
The voltage of the battery group should be equal to the DC voltage of the wind generator 
(after  rectification),  so  the  system  works  at  its  full  efficiency.  The  input  DC  voltage  of  a 
matched inverter should be equal to the working voltage of the wind turbine. 

 
5.1.4 The input DC voltage of the matched inverter should be    equal with working voltage of the 

wind generator (after rectification). 

 
5.2 Safety Notes 

5.2.1 Do not run the wind generator without any load, or run at a very high rotating speed for 

long periods of time. 

5.2.2  Check  the  tower  condition  regularly.  If  there  are  any  loose  components,  they  should  be 

tightened immediately, to prevent the wind turbine falling down.   

5.2.3 When running speed of the rotor is high, people should not stay under the wind turbine. 
5.2.4 When wind speed is more than 24 m/s, the wind turbine should be stopped manually. 
5.2.5 When vibration or strange noise is heard while the turbine is working, stop the wind turbine 

and find the reason to prevent damage. 

5.2.6  The  power  supply line  of the  wind generator  should be  run independently.  It  can not  be 

mixed used with other power supply lines. DC power supply is safer and more efficient for 
lights. For home electric appliances, an AC power supply line (from an    inverter) should 
be used. It is suggested that the connector of a refrigerator should be inserted in a special 
plug with a timer to control its usage.   

5.2.7.  When  connecting  the  wires  of  the  wind  generating  system,  the  battery  lines  must  be 

connected  to  the  controller  &  inverter  box  first,  then  connect  the  three  lines  from  the 
generator  to  the  controller.  When  disconnecting  the  wire  from  the  wind  generating 
system,  the  three  generator  lines  must  be  first  disconnected  from  the  controller,  then 
disconnect the two lines of the battery group from the controller & inverter box. 

5.2.8  The  “RUN  &  STOP”  switch  on  the  controller  &  inverter  box  should  keep  at  the  “RUN” 

position under normal conditions. Only toggle the switch to the “STOP” position when the 
batteries have been fully charged or to protect the system against storm winds,. It is not 
recommended to move the switch when wind is strong and rotor is rotating at high speed. 
Only change the switch to the “STOP” position when rotor is rotating slowly. 

5.2.9. The batteries should be installed in a place that is far from fire and heat sources. The gas 

generated from the charging and discharging process should be vented from the room. 

5.3.Keep the rotor balanced, eliminate vibrations 

If  the  blades  lose  balance  due  to  outside  damage  and  create  strong  vibrations,  the  wind 
generator must be stopped until the trouble is eliminated. The attached special tools should 
be  used  for  disassembling  the  rotor.  Remove  the  nut  and  washer  from  the  axes  end  of 
generator  first,  screw  the  special  sleeve  onto  the  hub firmly,  then  drive the  M16×30  screw 

Содержание 2KW WIND TURBINE

Страница 1: ...2KW WIND TURBINE Operation Manual GRADE AAA Please read carefully before using EST energy saving technology ESPECIALLY DESIGNED FOR EST LEBANON ...

Страница 2: ...DC48v Generator style Three phase permanent magnet Charging method Constant voltage current saving Speed regulation method Yawing Electromagnetic brake Stop method Manual brake Tower height m 6 Weight kg not including batteries or inverter Main unit 95 Total 155 3 Preparation 3 1 Prepare batteries according to manufacturers specifications 3 2 Unpack and check the turbine parts and verify all parts...

Страница 3: ...y 20cm Put the loop for guy wire through the loop welded to the tower section Close the loop with two wire clamps Repeat for each of the remaining cables 4 4 Put the heart ringer for steel wire across the o loop of turnbuckle and then rip the steel wire into the heart ringer Bend for a loop no less than 30cm long fasten with wire clamps Hook the turnbuckles of A B and D pits to the chain of anchor...

Страница 4: ...e steel wires to make the mast in its vertical position Strain the steel wire until it can rebound lightly when gives a transverse force 4 14 Check the wire block screw buckle and all connecting point Make sure it is safe Then wrap and blocked them with galvanized wire Put anti corrosive grease on wire block screw buckle and all links where necessary 4 15 Connect the batteries in series to be a gr...

Страница 5: ...ent damage 5 2 6 The power supply line of the wind generator should be run independently It can not be mixed used with other power supply lines DC power supply is safer and more efficient for lights For home electric appliances an AC power supply line from an inverter should be used It is suggested that the connector of a refrigerator should be inserted in a special plug with a timer to control it...

Страница 6: ...e free and low maintenance If the installation and operation are correct failures will not appear under normal conditions In case of failure please consult following table Trouble Reason Solution Wind generator vibrating strongly 1 Steel cable guy line is loose 2 Hub blade bolts are loose 3 Blade is defective caused by outside force 4 Ices over on the surface of blades causes imbalance 1 Tighten t...

Страница 7: ...e wires so as to reduce circuit electricity loss There is no output electric current in AC circuit of the Generator 1 There is a broken wire in the AC lines of the generator 2 There are circuit break in output line 3 Stator winding is burnt circuit is open Find out the reason and connect the wires 1 Find out the broken point then connect the wires 2 Disassemble then repair the damaged coil AC outp...

Страница 8: ...Fig1 2KW WIND TURBINE SYSTEM AAA ...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...HY 2KW WIND TURBINE WIRING DIAGRAM ...