26-1659-01
If the MCP is being flush mounted, cut off crimp fork terminals, strip ends for desired
length and twist conductor strands together neatly. After installing the back box securely,
attach the adaptor plate using the two screws provided, and terminate the MCP wires
into the flying terminal block.
The MCP is installed by locating the upper mounting hook into the receiver in the back box and
then pushing the unit gently home. The single fixing screw may then be tightened as required.
Connections
MAGDUO MCPs can be mixed on the same zone as other types of MAGDUO device The above diagram shows
how to make the zone positive, zone negative and screen connections between the control panel and MAGDUO
MCPs. Refer to the instruction leaflets supplied with other MAGDUO devices for their equivalent wiring/terminal
labelling details.
Please note that the E terminal on the MCPs should only be connected to the zone cable screen and NOT to the
bu
ilding earth. The cable screen is connected to earth at the panel end only, via the zone “SCRN” terminal (or
EARTH terminal on the MAGDUO panel). It is important to maintain the screen/earth continuity in order to protect
against data corruption from interference.
Remember that the device at the end of the line must have its EOL signal activated using the
relevant EOL switch. Do not use a resistor or capacitor
(or another manufacturer’s End of Line
device) as the end of line, as this may prevent correct operation of the zone.
Reset and Test
The MCP contains a re-settable element, which latches in position when
operated and does not need to be replaced. Inserting the key as shown and
turning it clockwise until the element clicks back into place will reset the unit.
Testing the MCP may be carried out either by pressing the element or by using
the key in the same manner as for resetting but without having pressed the
element.
E
BLUE
RED
YELLOW
Y
B
R