User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
29
i. Auto Set Clock: Automatically sets the internal clock to the current
date and time.
ii. Set Clock: Sets the internal clock to a date and time manually specified
in the date/time field.
iii. Auto Transmit: Enables/Disables the automatic transmission of status
information every 30 minutes.
iv. Internal Chart: Start or re-start the internal logging of electrical
parameters.
v. Ground Detection: Enables/Disables the ability of enVision to detect
and respond to an open Ground connection. Disabling may be
necessary in order to power enVision from a UPS output, but in
general it is highly recommended to leave this feature enabled.
vi. Overload Shutdown: Enables/Disables the ability of enVision to turn off
connected equipment when a current overload condition is detected.
After this occurs, the outlets will not be automatically turned back on.
vii. Power Fail Hold: When enabled, enVision will keep its outlets
off following a power outage or shutdown event. The outlets
must be manually turned back on using software or the
MENU and SCROLL buttons.
viii. Update ID: Sets the product identifier specified in the text box. 10
character limit.
ix. Update Limits: Sets the 6 voltage thresholds specified by the
voltage threshold selection fields. Press
Default
to select factory
default limits.
x
. Language: Select the software’s display language.
xi. Save: Save the current settings for reference.
Limit
When Activated
Action
Factory Default
120V
208/240V
Over Voltage
Shutdown
V > OV
Shutdown
Outlets turned
Off
and
event recorded
150
280
Over Voltage
Record
OV
Shutdown
> V > OV
Record
Outlets stay
On
and
event recorded
145
270
Over Voltage
Restore
V < OV
Restore
After OV
Shutdown
Outlets turned
On
and
event recorded
140
260
Under Voltage
Restore
V > UV
Restore
After UV
Shutdown
Outlets turned
On
and
event recorded
105
190
Under Voltage
Record
UV
Shutdown
< V < UV
Record
Outlets stay
On
and
event recorded
100
180
Under Voltage
Shutdown
V < UV
Shutdown
Outlets turned
Off
and
event recorded
80
160