background image

Page 2 of 4

 

  D A T A   S H E E T

 ESL85001-0632

 

Not to be used for installation purposes.

  Issue 1  

Application

The SafeAir 260-CO Carbon Monoxide Detector is intended for 
ordinary indoor-dwelling unit applications in both residential and 
commercial occupancies, including single/multiple family residential 
occupancies, hotel rooms, dorm rooms, and other areas approved 
by the authority having jurisdiction (AHJ). The 260-CO detector 
can connect to either UL 985 (Household Fire Warning) or UL 864 
(Commercial Fire) control panels. It is not intended for use in indus-
trial applications such as gasoline refineries or parking garages, 
which require different listings.

The 260-CO is a four-wire device that uses a Class 2 output from 
a control panel. Nonetheless, the primary alarm notification de-
vice remains the 260-CO’s internal sounder with the control panel 
secondary to these purposes. The 260-CO is not a substitute for life 
safety devices, and should be only considered as an integral part of 
a comprehensive safety program.

Selecting a suitable location is critical to the correct operation of 
CO detectors. Install the 260-CO in accordance with 

NFPA 720 

Standard for the Installation of Carbon Monoxide (CO) Detection 
and Warning Equipment.

 Place wall-mounted detectors at least 

5 ft. (1.5 m) up from the floor. For ceiling mounted applications, 
place the detector at least 1 ft. (0.3 m) from any wall.

Recommended CO detector locations:

 

9

Within 10 ft. (3 m) of all sleeping areas, including areas such 
as hotel rooms and dorm rooms.

 

9

In a suitable environment: areas with a temperature range 
of 40 to 100 °F (4.4 to 37.8 °C) and with a relative humidity 
range of 10 to 90% noncondensing.

 

9

In residential dwellings, locate detectors in every bedroom 
and on each level. At a minimum, place one detector outside 
the sleeping areas.

 

 Recommended locations for CO detectors

Always check with your local building codes,  

legislation, and Authority Having Jurisdiction  

for specific CO location requirements in your area

Recommended CO detector locations in commercial occupancies:

 

9

Outside each separate sleeping area in the immediate vicinity 
of the bedrooms (including areas such as hotel rooms and 
dorm rooms)

 

9

On every occupied level of a dwelling unit, including base-
ments, but excluding attics and crawl spaces

 

 

9

Centrally located on every habitable level of the building and 
in every HVAC zone based on an engineering evaluation con-
sidering potential sources and migration of carbon monoxide

 

9

On the ceiling in the same room as permanently installed fuel-
burning appliances

 

9

In any area required by local building codes, legislation, or the 
authority having jurisdiction

 

9

On a firm, permanent surface

Do not install the CO detector:

 

8

Within 5 ft. (1.5 m) of any cooking appliance

 

8

Within 10 ft. (3 m) of a fuel-burning appliance

 

8

Near air conditioners, heating registers, and any other ventilation 
source that may interfere with CO gas entering the detector

 

8

Where furniture or draperies may obstruct the airflow

 

8

In a recessed area

Operation

SafeTest functional test:

 This test facilitates the use of CO test 

spray to verify the correct operation of the detector, which is man-
datory per NFPA 720. The SafeTest mode is activated by pressing 
and holding the test/hush button for 5-10 seconds. While in Saf-
eTest mode, directing UL-classified CO testing spray at the sensor 
port will result in the activation of the alarm relay, and the sounder 
and red LED in a temporal-four pattern. Pressing and holding the 
test/hush will exit SafeTest mode. 

Distinct temporal-four sounder alarm: 

The 85 dB temporal-

four sounder provides a distinctive alarm notification that is easy 
to differentiate from smoke alarm notification devices. The alarm 
beeps four times, rests five seconds and then repeats the pattern. 

Test/hush button:

 Use the test/hush button to test the alarm and 

silence an activated alarm. Pushing the test/hush button silences 
the integral sounder for five minutes. The red alarm light stays on 
and if CO is still present after five minutes, the detector once again 
sounds in the temporal-four pattern.

End of sensor life indicator: 

The detector uses both a flashing 

green LED and intermittent sounder chirps to indicate that the de-
tector needs replacing. To silence the detector, push the test/hush 
button. The detector also begins signaling a trouble when the CO 
sensor is approaching end-of-life. 

Common trouble relay: 

The trouble relay opens to indicate a 

trouble condition upon lost power, CO sensor cell trouble, or cell 
end-of-life. When connected to a listed control panel, the trouble 
relay can report a trouble condition locally at the panel and option-
ally at the central station, if the system is monitored. 

WARNINGS: 

Connect the CO detector only to a zone dedicat-

ed exclusively for CO detection and that is monitored 24 hours 
a day. Do not connect to an initiating circuit with fire or security 
devices. Failure to properly install, test, and maintain a CO 
detector may cause it to fail, potentially resulting in loss of life.

Отзывы: