EsiWelma Srl

 

URS20SI_en.doc - rev. 0 

Oxygen detectors – URS20SI 

20/10/2010 

Gas detection systems for industrial environments 

1/8

 

 

 

 

 

 

Oxygen detectors 

IP65 protection rating 

 

URS20SI 

 

 

 

 

 

 

 

 

 

 

 

 

11…28Vdc power supply. 

Electrochemical cell sensor designed for the detection of oxygen (O

2

). 

Up to three alarm thresholds plus sensing element fail. 

LED on sensing element body to indicate operating status. 

Automatic countdown of sensor life.

 

Use 

The URS20SI detectors are used to detect oxygen excess or deficiency in non-
classified areas. 

An

 oxygen excess

 forms if it leaks in hospitals, laboratories, welding centres and, 

more in general, where oxygen is stored. 

Oxygen deficiency

 is an indirect measurement of the presence of other explosive or 

asphyxiant 

gases that deplete the oxygen in the air. 

URS20SI sensors can be used in stand-alone mode with 4…20mA output or with an 
optional voltage-free contact relay card having the following four digital outputs: 

- Pre-alarm, 1

st

 alarm threshold, 2

nd

 alarm threshold, sensor fail. 

Operation 

If there is an oxygen leak or an absence of oxygen, the detector compares the 
measured concentration value with the threshold limit setpoints and energises the 
associated relays. Information on the measured concentration value is always at the 
4…20mA output. 

Ordering 

To order, simply state the part number: 

URS20SI

For special versions, on request, please contact Customer Service. 

 

Содержание Sensigas URS20SI

Страница 1: ...nd more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SI sensors can be...

Страница 2: ...thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up to 200 at 1...

Страница 3: ...rs must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructions for location of the...

Страница 4: ...the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP swit...

Страница 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection s...

Страница 6: ...ectrical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommende...

Страница 7: ...tenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 ha...

Страница 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Отзывы: