Reflections in 1-Wire networks 

Each junction in a bus system causes an impedance mismatch at the junction. In addition, unwanted reflections 
are generated at the ends of a branch or also at the end, which can falsify or partially erase the useful signal. The 
longer a branch is, the more the mismatches and reflections appear. From this point of view, the star topology 
does not perform well. The different strands form branches with strong mismatching, which influence each other 
unfavorably. 
The 

star topology

 or 

tree topology

 is by far the most frequently used in practice, but requires more attention 

and care during installation and commissioning. Here the use of correct cable connectors, patch panels and 
termination (1-Wire Term 1) is very important. 
 
The preferred topology is the 

linear topology

, since almost no reflections occur at branch lengths of less than  

3 m. The highest reliability is achieved with this topology. In practice, however, it is the most difficult and costly 
installation to implement. Here, too, termination must be provided at the end of the cable. 
 
The 

branch topology

 occupies an intermediate position. Reflections can already be expected here. However, 

these do not necessarily have to be disturbing, especially if the length is not too long. In small networks with a 
total length of less than 50 m, the choice of the correct topology is not so critical. 
 
All network topologies have in common that the line ends should be terminated. Here the ESERA 1-Wire Term 1 
module is a very good and practical solution.   
 

10 

Operating conditions 

The module may only be operated at the specified voltages and ambient conditions. The device can be operated 
in any position. The device is intended for use in dry and dust-free rooms. If condensation is formed, allow at least 
2 hours for the unit to acclimatize. Do not operate the module in an environment in which flammable gases, 
vapors or dusts are present or could be present.  
 

 

11 

Disposal instructions  

Do not dispose of the device in domestic waste! Electronic devices must be disposed of at 
the local collection points for electronic waste in accordance with the Directive on Waste 
Electrical and Electronic Equipment! 
 

12 

Safety instructions 

When using products that come into contact with electrical voltage, the valid VDE regulations must be 
observed, especially VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711 and VDE 0860 

 

All final or wiring work must be carried out with the power turned off. 

 

Before opening the device, always unplug or make sure that the unit is disconnected from the mains. 

 

Components, modules or devices may only be put into service if they are mounted in a contact proof housing. 
During installation they must not have power applied. 

 

Tools may only be used on devices, components or assemblies when it is certain that the devices are disconnected 
from the power supply and electrical charges stored in the components inside the device have been discharged. 

 

Live cables or wires to which the device or an assembly is connected, must always be tested for insulation faults or 
breaks. 

 

If an error is detected in the supply line, the device must be immediately taken out of operation until the faulty cable 
has been replaced. 

 

When using components or modules it is absolutely necessary to comply with the requirements set out in the 
accompanying description specifications for electrical quantities. 

 

If the available description is not clear to the non-commercial end-user what the applicable electrical characteristics 
for a part or assembly are, how to connect an external circuit, which external components or additional devices can 
be connected or which values these external components may have, a qualified electrician must be consulted. 

 

It must be examined generally before the commissioning of a device, whether this device or module is basically 
suitable for the application in which it is to be used. 

 

In case of doubt, consultation with experts or the manufacturer of the components used is absolutely necessary. 

 

For operational and connection errors outside of our control, we assume no liability of any kind for any resulting 
damage. 

 

Kits should be returned without their housing when not functional with an exact error description and the 
accompanying instructions. Without an error description it is not possible to repair. For time-consuming assembly or 
disassembly of cases charges will be invoiced. 

 

During installation and handling of components which later have mains potential on their parts, the relevant VDE 
regulations must be observed. 

 

Devices that are to be operated at a voltage greater than 35 VDC / 12mA, may only be connected by a qualified 
electrician and put into operation. 

 

Commissioning may only be realized if the circuit is built into a contact proof housing. 

Содержание 1-Wire Controller 1

Страница 1: ... the 1 Wire network Active termination 1 Wire Term 1 is highly recommended for increasing the maximum line length and improving the system stability of the 1 Wire network especially with long 1 Wire lines and with a setup in star or tree topology In a 1 Wire network up to 3 pieces of 1 Wire Term 1 modules can be connected The 1 Wire Term 1 is very compact and can be ideally installed in a flush mo...

Страница 2: ...ESD EN 61000 4 3 HF EN 61000 4 4 Burst EN 61000 4 5 Surge EN 61000 6 1 interference immunity EN 61000 6 3 interference radiation RoHS 7 Integration in 1 Wire Network The 1 Wire Term 1 module is mounted at the end of a 1 Wire network cable If the 1 Wire network is star shaped i e with several 1 Wire cable sections a 1 Wire Term 1 module should be connected to each end No more than three 1 Wire Term...

Страница 3: ... the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11355 V2 0 R1 0 Manual Page 3 of 5 8 Connection example Note Basics and tips for the 1 Wire bus system can be found in our eBook in the shop at https www esera de service support 1 wire grundlagen ...

Страница 4: ...aste Electrical and Electronic Equipment 12 Safety instructions When using products that come into contact with electrical voltage the valid VDE regulations must be observed especially VDE 0100 VDE 0550 0551 VDE 0700 VDE 0711 and VDE 0860 All final or wiring work must be carried out with the power turned off Before opening the device always unplug or make sure that the unit is disconnected from th...

Страница 5: ...affected If defects occur for which the ESERA GmbH is responsible and in the case of replacement goods the replacement is faulty the buyer has the right to have the original purchase price refunded or a reduction of the purchase price ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We a...

Отзывы: