Device Profile Area
CAN-CBX-AI814
Manual • Doc.-No.: C.3020.21 / Rev. 1.5
Page 89 of 108
8.10.7 Global Interrupt Enable (6423
h
)
Index
Sub-
index
Description
Value range
[Boolean]
Default
[Boolean]
Data
type
Access
mode
6423
h
0
Analog_Input_Global_Interrupt_Enable
true, false
false
boolean
rw
With the object Analog Input Global Interrupt Enable the interrupt-function of the module is
enabled or disabled. The values in object 6421
h
and 6426
h
remain unaffected of this.
In the default-setting the interrupts, triggered by a change of the analog input value, are disabled.
Value range:
Analog_Input_Global_Interrupt_Enable = true => Global Interrupt enabled
Analog_Input_Global_Interrupt_Enable = false => Global Interrupt disabled (default setting)
Note:
To enable an event controlled transmission of the TxPDO it is absolutely necessary to
set Analog_Input_Global_Interrupt_Enable to ‘true’.