Interfaces and Connector Assignments
8.7 Conductor Connection/Conductor Cross Sections
The following table contains an extract of the technical data of the cable plugs.
Characteristics
Connector Type
Power Supply
Voltage 24 V
CAN Connector
Connector type plug component
(Range of articles)
FKCT 2,5/..-ST KMGY
FK-MCP 1,5/5-STF-
3,81
Connection method
spring-cage
connection
screw
connection
Stripping length
10 mm
9 mm
Conductor cross section solid min. / max.
0.2 / 2.5 mm²
0.14 / 1.5 mm²
Conductor cross section stranded min. / max.
0.2 / 2.5 mm²
0.14 / 1.5 mm²
Conductor cross section stranded, with ferrule without
plastic sleeve min. / max.
0.25 / 2.5 mm²
0.25 / 1.5 mm²
Conductor cross section stranded, with ferrule with plastic
sleeve min. / max.
0.25 / 2.5 mm²
0.25 / 0.5 mm²
Conductor cross section AWG/kcmil min. / max.
24 / 12
26 / 16
2 conductors with same cross section, without TWIN
ferrules with plastic sleeve
not allowed
not allowed
2 conductors with same cross section, stranded, TWIN
ferrules with plastic sleeve, min./ max.
0.5 / 1.0 mm²
not allowed
Minimum AWG according to UL/cUL
26
28
Maximum AWG according to UL/cUL
12
16
1
Technical Data from Phoenix Contact website, printed circuit board connector, plug component
CAN-EtherCAT
Manual • Doc. No.: C.2922.21 / Rev. 1.4
Page 75 of 92