GD350A series high-performance multifunction VFD
-179-
Function
code
Name
Description
Default Modify
38–40: Reserved
41: C_Y1 from PLC (Set P27.00 to 1.)
42: C_Y2 from PLC (Set P27.00 to 1.)
43: C_HDO from PLC (Set P27.00 to 1.)
44: C_RO1 from PLC (Set P27.00 to 1.)
45: C_RO2 from PLC (Set P27.00 to 1.)
46: C_RO3 from PLC (Set P27.00 to 1.)
47: C_RO4 from PLC (Set P27.00 to 1.)
48: PT100 temperature pre-alarm
49: PT1000 temperature pre-alarm
50–63: Reserved
P06.05
Output terminal
polarity selection
The function code is used to set the polarity of
output terminals.
When a bit is 0, the input terminal is positive;
When a bit is 1, the input terminal is negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y
Setting range: 0x0–0xF
00
○
P06.06 Y1 switch-on delay
The function codes specify the delay time
corresponding to the electrical level changes
when the programmable output terminals
switch on or switch off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000–50.000s
Note:
P06.08 and P06.09 are valid only
whenP06.00=1.
0.000s
○
P06.07 Y1 switch-off delay
0.000s
○
P06.08
HDO switch-on
delay
0.000s
○
P06.09
HDO switch-off
delay
0.000s
○
P06.10
RO1 switch-on
delay
0.000s
○
P06.11
RO1 switch-off
delay
0.000s
○
P06.12
RO2 switch-on
delay
0.000s
○
P06.13
RO2 switch-off
delay
0.000s
○
P06.14
AO1 output
0: Running frequency (0–Max. output
frequency)
0
○
P06.15
Reserved
0
○