8

 

 

(1)

 

Single system capacity based on 30 min. fill requirement of largest single sprinkler system; a secondary air compressor with normally 
closed isolation valve can be used to meet fill requirement for larger individual systems

 

(2)

 

Size and weight of nitrogen generator only, does not include separate air compressor

 

(3)

 

All nitrogen generators include 1 year manufacturer

s warranty per ECS terms and conditions

 

 

Wall Mount

 

Skid Mount

 

Stand Alone w/Separate Air Compressor

 

PGEN

-

3

 

PGEN

-

5

 

PGEN

-

10

 

PGEN

-

20

 

PGEN

-

30

 

PGEN

-

40

 

PGEN

-

50

 

PGEN

-

60

 

Total System Capacity

 

675 gal

 

950 gal

 

2,000 gal

 

3,200 gal

 

6,500 gal

 

11,000 gal

 

18,500 gal

 

22,500 gal

 

Single System Capacity @ 40 psi

(1)

 

215 gal

 

265 gal

 

560 gal

 

950 gal

 

1,150 gal

 

1,440 gal

 

2,025 gal

 

2,900 gal

 

Single System Capacity @ 20 psi

(1)

 

540 gal

 

590 gal

 

1,120 gal

 

1,800 gal

 

2,300 gal

 

2,880 gal

 

4,050 gal

 

5,800 gal

 

Air Compressor

 

Integral

 

Integral

 

Integral

 

Integral

 

Separate

 

Separate

 

Separate

 

Separate

 

Size (H x W x D)

 

36x24x9

 

36x24x9

 

38x29x11

 

57x32x40

 

Weight

 

115 lbs

 

125 lbs

 

175 lbs

 

420 lbs

 

152 lbs

(2)

 

264 lbs

(2)

 

300 lbs

(2)

 

300 lbs

(2)

 

Engineered Corrosion Solutions 

 11336 Lackland Road 

 St. Louis, MO 63146 

 Phone 1-314-432-1377 



www.ecscorrosion.com 

Содержание PGEN-30

Страница 1: ...acement Filters PGEN FKS Annual Maintenance Gas Membrane PGEN MS 20 Year Expected Service Life The ECS Protector Nitrogen Generator is designed for use in maintaining supervisory gas and facilitating...

Страница 2: ...storage and manual bypass Power supply 120 VAC 1 phase 60Hz 230 VAC 1 phase 50Hz Single point nitrogen air discharge NPT Hour Run Meter Cycle Counter The ECS Nitrogen Generator includes the following...

Страница 3: ...Power Supply The ECS Protector Nitrogen Generator requires a dedicated power supply to prevent interruption from other equipment The incoming power supply line ties into the top of the terminal block...

Страница 4: ...ng where used The nitrogen generator cabinet has two 2 system signals and five 5 outputs that can be monitored by the facility s BMS or fire alarm system The nitrogen generator is operating in the byp...

Страница 5: ...N 30E is part number PGEN FKS When maintained properly the nitrogen separation membrane will provide up to 20 years of service life Filter Replacement Procedure Preliminary Steps taking the nitrogen g...

Страница 6: ...ce the filter housing bowl has been unscrewed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge Di...

Страница 7: ...TIGHTEN ONLY Step 9 Replace the filter housing bowl by screwing it onto the filter housing top Important HAND TIGHTEN ONLY Step 10 Tighten the petcock valve to the closed position Step 11 The ECS Pro...

Страница 8: ...N 10 PGEN 20 PGEN 30 PGEN 40 PGEN 50 PGEN 60 Total System Capacity 675 gal 950 gal 2 000 gal 3 200 gal 6 500 gal 11 000 gal 18 500 gal 22 500 gal Single System Capacity 40 psi 1 215 gal 265 gal 560 ga...