ESC PGEN-30 Скачать руководство пользователя страница 1

1

 

 

ECS Protector Nitrogen Generator

 

PGEN

-

30 (PGEN

-

30E)

 

 

 

Specifications

 

Dimensions (cabinet):

 

24.5”(

W) x 

52.5”(

H) x 

8.5”(

D) 

 

(622mm(W) x 1,334mm(H) x 216mm(D))

 

Dimensions (incl. bypass):

 

32.5”(

W) x 

52.5”(

H) x 

8.5”(

D) 

 

(826mm(W) x 1,334mm(H) x 216mm(D))

 

Weight:

 

 

152 Lbs (69 Kg)

 

Temperature Range:

 

40°F 

-

 105°F (5°C 

-

 40°C)

 

Power Supply:

 

120v/1 phase/60Hz 

-

 Dedicated Circuit

 

(230v/1 phase/50Hz 

-

 Dedicated Circuit)

 

Power Consumption:

 

2 Amps

 

Gas Connections:

 

Air Inlet 

-

 ½

” 

NPT Female

 

 

Nitrogen Outlet 

-

 ½

” 

NPT Female

 

Drain Connection:

 

¼

” 

NPT Female

 

 

UL 508A Listed Industrial Control Panel

 

ECS Protector

 

Nitrogen Generator 

 

 

designed for fire sprinkler systems 

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) 

June 2018 - Rev 5 

Engineered Corrosion Solutions 

 11336 Lackland Road 

 St. Louis, MO 63146 

 Phone 1-314-432-1377 



www.ecscorrosion.com 

General Description

 

Ordering Information

 

 

Stock Number:

   

PGEN

-

30 (PGEN

-

30E)

 

Replacement Filters:

 

PGEN

-

FKS 

-

 Annual Maintenance

 

Gas Membrane:

 

PGEN

-

MS 

-

 20 Year Expected Service Life)

 

The  ECS  Protector  Nitrogen  Generator  is  designed  for 
use  in  maintaining  supervisory  gas  and  facilitating  the 

Dry  Pipe  Nitrogen  Inerting  (DPNI)

  process  for           

controlling oxygen corrosion in dry  and pre

-

action fire 

sprinkler  systems.    The  ECS  Protector  is  an  on

-

site    

nitrogen  generation  system  that  is  designed  to  be    
installed  inline  between  the    compressed  air  supply 
and the sprinkler system riser in dry or preaction pipe 
sprinkler  systems.  The  nitrogen  generator  utilizes 

membrane  gas  separation  technology  that  exhausts 
oxygen  as  a  waste  gas  to    produce  98%+  nitrogen  on 
demand with no nitrogen storage necessary for dry or 
preaction systems.

 

The  ECS  Protector  Nitrogen  Generator  cabinet  has  an 
external  bypass  valve  to  allow  for  nitrogen  generator 
maintenance  or 

fast  fill

” 

needs,  and  is  designed  to 

meet  the  NFPA  13  30

-

minute  fill  requirement  for  dry 

pipe or preaction fire protection systems. 

 

For use under U.S. Patents

 

8,720,591, 9,144,700 and 9,186,533

 

Содержание PGEN-30

Страница 1: ...acement Filters PGEN FKS Annual Maintenance Gas Membrane PGEN MS 20 Year Expected Service Life The ECS Protector Nitrogen Generator is designed for use in maintaining supervisory gas and facilitating...

Страница 2: ...storage and manual bypass Power supply 120 VAC 1 phase 60Hz 230 VAC 1 phase 50Hz Single point nitrogen air discharge NPT Hour Run Meter Cycle Counter The ECS Nitrogen Generator includes the following...

Страница 3: ...Power Supply The ECS Protector Nitrogen Generator requires a dedicated power supply to prevent interruption from other equipment The incoming power supply line ties into the top of the terminal block...

Страница 4: ...ng where used The nitrogen generator cabinet has two 2 system signals and five 5 outputs that can be monitored by the facility s BMS or fire alarm system The nitrogen generator is operating in the byp...

Страница 5: ...N 30E is part number PGEN FKS When maintained properly the nitrogen separation membrane will provide up to 20 years of service life Filter Replacement Procedure Preliminary Steps taking the nitrogen g...

Страница 6: ...ce the filter housing bowl has been unscrewed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge Di...

Страница 7: ...TIGHTEN ONLY Step 9 Replace the filter housing bowl by screwing it onto the filter housing top Important HAND TIGHTEN ONLY Step 10 Tighten the petcock valve to the closed position Step 11 The ECS Pro...

Страница 8: ...N 10 PGEN 20 PGEN 30 PGEN 40 PGEN 50 PGEN 60 Total System Capacity 675 gal 950 gal 2 000 gal 3 200 gal 6 500 gal 11 000 gal 18 500 gal 22 500 gal Single System Capacity 40 psi 1 215 gal 265 gal 560 ga...