2.2 STANDARD FEATURES

Code

Description

B10b

Manual activation of every single output from keyboard

By keyboard, it is possible to activate manually and individually every single output for an operation test.
Press key C to select the desired output to be activated. Press key A to activate the output.
The output is holded active for all the time that key A is pressed. It allows to measure the output voltage by using a

 

tester.

In case of anomalous operating, do this test with electrovalves disconnected.

B1b

Select Number of outputs

The selection of the number of outputs to be control led is connected by keyboard in SET MODE. If you set 0 or AUTO

 

in this function the sequencer will automatically select the connected loads by skipping the non connected ones.

 

Minimum load 5W ÷ 12 W depending on the output voltage. If the load is below of the minimum,  the autoselection does

 

not work correctly, set the number of outputs in set up.

B2x

Activation time from 0.05 to 5.00 sec.

B3x

Interval time from 1 to 999 sec.

If the pulse time is lower than 1 sec. it is possible to set any interval time value in the range indicated.
If the activation time is higher than 1 sec. the minimum settable interval time is:
Minumum interval time = 5 times pulse time (B2x)

B8b

Short-circuit protection of every single output

In case of short-circuit, the corresponding output is automatically skipped. Relay K2 will signal the alarm condition and

 

display will show the alarm situation code E1 (See the alarm description).

Press key E to reset the alarm.

C0

Input activation from external contacts

In Set up you can activate or deactivate the control of all the inputs of the device.
If inputs are deactivated, they are considered as always closed and no jumper is required on the terminal board.
Use a jumper for unused inputs if you activate them.
NOTE: all inputs of the device have to be connected to external contact without voltage.

C6

ON/OFF cleaning cycle from external pressure switch

If contact C6 is open, the cleaning cycle stops at the end of the whole cleaning cycle and the display shows 'P', which

 

means stop for low dP.

If contact C6 is closed, the cleaning cycle restarts from the beginning.
NOTE C6: Use a jumper for C6 if it is not used with active inputs (see F01).

D1a

Additional cycles after fan stop

By connecting an auxiliary volt-free contact of the fan circuit with the sequencer, it is possible to add a well-defined

 

number of cleaning cycles after the stop of the fan. Their number is selectable from 0 to 99 from the keyboard.

The activation of post-cleaning cycles starts even if C6 contact is open.
If contact D1a is open, the display shows '-0-' to indicate cycle stop for fan Off.
During the cycles after the fan stop, the decimal points blink on the display.
NOTE D1a: Link D1a clamps if it is not used with active inputs (see F01).

D6

ON/OFF Cleaning cycle from external contact.

If contact D6 is open, the cleaning cycle is not enabled and the display shows 'OFF'.
With sequencer with digital dP control the display shows 'OFF' and the dP reading alternatively.
By closing D6, the cleaning cycle can start from the first electrovalve
NOTE D6: Link D6 clamps if it is not used with inputs from external contact active. (see 5.1 : SETUP F01).

G1

Maximum load power 25W per output

HV

Input / Output voltage selection.

Use the jumpers on the board to select the supply voltage and the output voltage on the electrovalves. (See the board

 

layout).

JP1: Supply voltage selection between 115VAC and 230VAC.
JP2: Output voltage selection between 24, 115, 230 V (Only with 115VAC or 230VAC power supply).
JP3: Output voltage selection between AC and DC only with JP2 set to 24V.
WARNING: set F08 (PB/BB) or F16 (PC/BC) to the same output voltage that has been selected by means of the

 

jumpers to adjust the shortcircuit threshold. Otherwise, this might cause any malfunction or damage to the sequencer.

Содержание SEQUENCER FOR DEDUSTING PLANTS

Страница 1: ...dedusting plant cleaning cycle control without digital dP 2 1 STANDARD FEATURES B10b Manual activation of every single output from keyboard B1b Select Number of outputs B2x Activation time from 0 05 to 5 00 sec B3x Interval time from 1 to 999 sec B8b Short circuit protection of every single output C0 Input activation from external contacts C6 ON OFF cleaning cycle from external pressure switch D1a...

Страница 2: ... all inputs of the device have to be connected to external contact without voltage C6 ON OFF cleaning cycle from external pressure switch If contact C6 is open the cleaning cycle stops at the end of the whole cleaning cycle and the display shows P which means stop for low dP If contact C6 is closed the cleaning cycle restarts from the beginning NOTE C6 Use a jumper for C6 if it is not used with ac...

Страница 3: ...ly if necessary verify if there is dust on the enclosure of the device and remove it if it is present by using wet cloth 3 9 For supply voltages cabling and voltages applicable to the relay contacts follow the current rules 3 10 For all input control signals to the Timer D1a D5 D6 use anti flame wires with a minimum section of 0 5 mm 3 11 For the electrical connection of the supply voltage and fil...

Страница 4: ...ed 1 Disable 0 1 C0 1 F02 Pulse time from 0 05 to 5 00 sec 0 05 5 00 B2x 0 50 F03 Interval time between ev from 1 to 999 sec 1 999 B3x 005 F04 Selection Number of electrovalves 0 Automatic selection of the load 1 xx Set number of solenoid valves 0 32 B1b 000 F05 Number additional cycles after fan stop 0 99 D1a 002 F06 TEST Manual activation of every single ev from keyboard Key A Activate solenoid ...

Страница 5: ... C6 open See 2 2 C1d Additional cycles after ventilator stop active Blinking points D1a Pause time between ev scroll bar B3x 7 1 DISPLAY INDICATIONS WITH ALARM DISPLAY DESCRIPTION E1 05 Overload output 05 Example Display blinking Check the ev connection state of the coil of the ev indicated on display and possible presence of water inside the electric connector of the ev 8 1 INFORMATION AND GUIDE ...

Страница 6: ...9 1 WIRING DIAGRAM ...

Страница 7: ...10 1 ELECTRONIC BOARD SIZE AND VOLTAGE SETTINGS ...

Страница 8: ...11 1 ENCLOSURE DIMENSIONS ...

Страница 9: ...he microprocessor could be modified by external factor Switch Off the supply voltage of the sequencer Hold down key B and switch on the supply voltage By means of this operation the default data are loaded in set up Adjust the zero dP reading and the other parameters according to the filter s needs 13 1 WARRANTY The warranty lasts 4 years The company will replace any defective electronic component...

Страница 10: ... The object of the declaration described above is in conformity with the relevant Union harmonisation legislation The object of the declaration described above is in conformity with the relevant Union harmonisation legislation Directives 2014 30 UE 2014 35 UE and 2011 65 UE Directives 2014 30 UE 2014 35 UE and 2011 65 UE The following harmonised standards and technical specifications have been app...

Отзывы: