Appendix C. ENIP-2: IEC 60870-5-101 and IEC 60870-5-104
ENIP-2, manual, ENIP.411187.002. Rev. 11.2020
73
Appendix C. ENIP-2: IEC 60870-5-101 and IEC 60870-5-104
Available ASDU
Value
ASDU
Description
Digital
signals
1
M_SP_NA_1 Single-point information
3
M_DP_NA_1 Double-point information
30
M_SP_TB_1
Single-point information with time tag CP56
31
M_DP_TB_1 Double-point information with time tag CP56
Measured
value
11
M_ME_NB_1 Measured value, scaled value
13
M_ME_NC_1 Measured value, short floating point value
35
M_ME_TE_1 Measured value, scaled value with time tag CP56
36
M_ME_TF_1 Measured value, short floating point value with time tag CP56
Integrated
totals
15
M_IT_NA_1
Integrated totals
37
M_IT_TB_1
Integrated totals with time tag CP56
Default register
’
s addresses of ENIP-2-
…
-
Х
1:
address
Parameter
ASDU type
Quantum (for
type 11,13,35,37)
Digital signals
1000
DO1 ON
(ENMV-
1/2 №1)
1/30
3/31
-
1001
DO2 OFF
(ENMV-
1/2 №1)
1/30
-
1002
DO3 ON
(ENMV-1/2
№2)
1/30
3/31
-
1003
DO4 OFF
(ENMV-1/2
№2)
1/30
-
1004
DO5 ON
(ENMV-1/2
№3)
1/30
3/31
-
1005
DO6 OFF
(ENMV-1/2
№3)
1/30
-
1006
DO7 ON
(ENMV-1/2
№4)
1/30
3/31
-
1007
DO8 OFF
(ENMV-1/2
№4)
1/30
-
1
DI1
(ENIP)
1/30
3/31
-
2
DI2
(ENIP)
1/30
-
3
DI3
(ENIP)
1/30
3/31
-
4
DI4
(ENIP)
1/30
-
5
DI5
(ENIP)
1/30
3/31
-
6
DI6
(ENIP)
1/30
-
7
DI7
(ENIP)
1/30
3/31
-
8
DI8
(ENIP)
1/30
-
RMS
100
Ua
11/13/35/36
Uquant, V
101
Ub
11/13/35/36
Uquant, V
102
Uc
11/13/35/36
Uquant, V
103
Average U
11/13/35/36
Uquant, V
104
Uab
11/13/35/36
Uquant, V
105
Ubc
11/13/35/36
Uquant, V
106
Uca
11/13/35/36
Uquant, V
107
Average line-to-line U
11/13/35/36
Uquant, V
108
Ia
11/13/35/36
Iquant, A
109
Ib
11/13/35/36
Iquant, A
110
Ic
11/13/35/36
Iquant, A
111
Average I
11/13/35/36
Iquant, A
112
Pa
11/13/35/36
Pquant, W
113
Pb
11/13/35/36
Pquant, W