4 Installation Instructions
Page 14
Starting delay
When multiple appliances start at the same time, some appliances may
not get enough tension (230V) or gas(pressure)
The BCU (lid) has a potentiometer (t
E
) with which per appliance a start
delay of 0-60 seconds can be set. Per appliance a delay of 5-10
seconds should suffice.
The following settings are set by the producer and should NOT be altered.
Changes might lead to damage!
Cooling down period:
A standard of 10 seconds cooling down period is set but a longer period
can be set. The middle potentiometer can add 0 to 100 seconds.
For this appliance it is set to 50 seconds extra.
Minimal burning time
Every time a appliance starts, there is a short incomplete combustion
A minimal burning time can be set with the left potentiometer, with
which also life expectancy of relays, engine and other parts can be
lengthened. (Only necessary when room thermostat is set too sensitive)
Range: 0-180 Seconds. For this appliance it is set to 60 seconds extra.
Put the BCU lid
straight
back to its socket and tighten it with the screws.