D05125R01.20
F-PRO 116 User Manual
5-9
64/51
–
IDMTL SEF Protection Logic diagram
Figure 5.8: Logic Diagram of 64/51 Function
Table 5.9: 64/51SEF - Inverse Time Sensitive /Restricted Earth Fault
Setting Description
Range
Function Activation
Enable/Disable
Pickup ISEF
0.005 to 3.000 (1 A) / 0.025 to 15.000 (5 A)
Curve Type
For details see Table 5.3
“IEC and IEEE Curves”
TMS
0.01 to 10.00
Pickup DTL Delay
0.00 to 999.99 seconds if chosen for DTL characteristics
Reset Delay
DTL / ANSI Decay (other than DTL selection)
Reset DTL Delay
0.0 to 99.9 seconds if DTL is chosen
A
0.0010 to 1000.0000 settable if chosen for user defined
characteristics
B
0.0000 to 10.0000 settable if chosen for user defined
characteristics
p
0.01 to 100.00 settable if chosen for user defined
characteristics
TR
0.10 to 150.00 settable if chosen for user defined
characteristics
Inrush Blocking
Enable/disable
Содержание F-PRO 116
Страница 2: ......
Страница 12: ...1 2 F PRO 116 User Manual D05125R01 20 Figure 1 1 F PRO 116 Relay Function Line Diagram...
Страница 16: ...1 6 F PRO 116 User Manual D05125R01 20 Figure 1 4 Ordering Template...
Страница 20: ......
Страница 30: ......
Страница 84: ...7 12 F PRO 116 User Manual D05125R01 20 Figure 7 10 Point Map...
Страница 94: ......
Страница 96: ......
Страница 124: ......
Страница 148: ......
Страница 149: ...D05125R01 20 F PRO 116 User Manual Appendix H 1 Appendix H Mechanical Drawings H 1 Front View...
Страница 150: ...Appendix H 2 F PRO 116 User Manual D05125R01 20 H 2 Rear View...
Страница 151: ...D05125R01 20 F PRO 116 User Manual Appendix I 1 Appendix I AC Schematic Drawing...
Страница 152: ......
Страница 153: ...D05125R01 20 F PRO 116 User Manual Appendix J 1 Appendix J DC Schematic Drawing...
Страница 154: ......
Страница 155: ...D05125R01 20 F PRO 116 User Manual Appendix K 1 Appendix K Connection Diagram...
Страница 156: ......