![Ericsson MINI-LINK AMM 1U-1 Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/ericsson/mini-link-amm-1u-1/mini-link-amm-1u-1_installation-manual_2423528056.webp)
MINI-LINK High Capacity Indoor Installation Manual
Fusing the Power Supply
Each MMU and fan unit must have its own fuse. We recommend you to use a
DDU (see
DC Distribution Unit Installation Instruction
). For other cases follow
the instruction below:
Negative earth
Positive earth
Power
supply
Power
supply
DC+
DC-
+
-
Fuse
MMU
DC-
DC+
+
-
Fuse
MMU
4057
Figure 60
How to fuse the power supply
23. Fuse the power supply as shown in the figure above.
Recommended fuses:
•
5 A minimum 100 V of type F with ceramic body and high breaking capacity
according to UL/CSA 248-14.
•
4 A minimum 100 V of type F with ceramic body and high breaking capacity
according to IEC 127.
Power Supply
Input DC Voltage:
24 – 60 V, nominal (20.4 – 72.0 V including tolerance).
See marking on the MMU for information.
Caution!
The equipment must be supplied by a double/reinforced SELV source. A circuit
breaker with a rating of maximum 16 A must be incorporated into the circuit.
50