ERICO TDS150-1SR Series Скачать руководство пользователя страница 2

   INSTRUCTION SHEET

 

 

 

TECHNICAL SUPPORT:       IPCR1502 REV. 5    

2 of  2         

IPCR1502_5.DOC 

                                                    

www.erico.com                                                                                         

ESN12623

 

 

 

§ 

The location of this enclosure prevents the temperature of the 
TDS unit(s) from exceeding its maximum specified rating. 

§ 

Adequate electrical and safety protection is provided by the 
enclosure to all exposed terminals. 

§ 

The location and type of enclosure meets the specified 
environmental requirements and prevents the ingress of 
moisture and water. 

§ 

The indicator status of the TDS can be readily inspected. 

5.  ELECTRICAL CONNECTION  

When connecting the TDS on the input side of the distribution panel 
wiring, it is usual to wire the TDS L-N (L1, L2, L3 to N on 3 phase 
systems). When connecting the TDS to the output side of the panel 
wiring, it is usual to wire it L-PE/PEN.  

§ 

On TN-C networks, three TDS units are required. L1, L2, L3 
should be protected to PEN.  

§ 

On TN-S networks, four TDS units are required.  L1, L2, L3 
should be protected to N, and N should be protected to PE. 

§ 

On TT networks, three TDS units and a SGD unit are required.  
L1, L2, L3 should be protected to N using the TDS units, and N 
should be protected to PE using the SGD unit. 

§ 

On IT networks, four TDS units are required. L1, L2, L3, N 
should be protected to PE using 440V TDS units on a normal 
230V system. 

§ 

On the TDS1100 series, a “Kelvin” type connection can be 
made using separate input and output terminal pairs. This 
configuration helps reduce the effects of lead length. The 
maximum load current under such a configuration should be 
limited to 125A. 

6.  WIRING 

The interconnecting wiring should: 

§ 

Be as short as possible - not exceeding 300mm (12”). 

§ 

Avoid sharp bends >100mm radius is recommended. 

§ 

Have the conductors twisted together where possible. 

§ 

Terminals will allow connection of 25mm² (#4AWG) multi-
strand wiring or 35mm² (#2AWG) solid – ref. Table 1. The wire 
insulation should be stripped back 8mm (5/16"). 

7.  RESIDUAL CURRENT DETECTORS (RCD) 

When an RCD is used, it is preferable that the TDS modules be 
installed prior to (upstream of) this device to avoid nuisance tripping 
which may occur during transient activity. 

8.  FUSING AND ISOLATION 

Overcurrent protection must be installed in the upstream circuit of 
every TDS unit if the mains supply is > 100A. This is to provide 
protection to the TDS, the load and the wiring in the case of a fault 
– ref. Table 1 for suitable fuse ratings. 

NOTE:

 Operation of this over-current protection under excessive 

surge conditions may occur removing protection from the circuit. 
The Remote Status contacts should be monitored for this 
possibility. 

9.  STATUS INDICATION 

TDS modules incorporate an internal thermal disconnect element, 
which automatically disconnects the varistor from the network in the 

event of a thermal overload. Should the internal disconnect 
operate, a red flag appears in the transparent window of the Status 
Indicator(s) on the front of the TDS. 

10.  MAINTENANCE & TESTING 

Before removing a TDS module from service, ensure that the power 
has been removed and if possible “locked out”. Qualified personnel 
should only undertake replacement of TDS modules. Replacement 
plug-in modules are available.  

NOTE:

 It is very important to ensure that the new module is of the 

same type and voltage as that being replaced. 

NOTE:

 TDS units should be inspected periodically, and also 

following any periods of lightning or transient voltage activity. Check 
the Status Indicator and replace the module if required. 

11.  REMOTE STATUS 

The TDS provides remote status monitoring via voltage-free 
contacts. Failure of the TDS is signified by the N/C contacts (11,14) 
opening and the N/O contacts (11,12) closing. Ensure that the 
voltage and current ratings of the contacts are not exceeded. 

NOTE:

 

The TDS contacts are

 independent of whether power is 

supplied, or not, to the TDS module. The status of the 
contacts is given solely by the failure status of the TDS 
module. 

 

Table 1. TDS operating specifications 

 

Max. continuous operating 
voltage, Uc (AC) 

170, 275, 320, 610 Vac 

(Important: ensure correct TDS is 
selected, Uc must be higher than 
power frequency voltage). 

Max Torque 

4.5N.m./40in-lbs 

Main terminals – wire cross 
section / backup fuse 

multi-strand 25 mm2 (#4AWG) 
(single-strand 35 mm

2

(#2AWG)) / 

max. 125 AgL 

Remote status contacts 

0.5 A / 250 VAC; 3 A / 125 VAC 
1.5 mm

2

 wire cross section 

 

Отзывы: