ERICO Pentair TDS Series Скачать руководство пользователя страница 2

 

The location of this enclosure prevents the temperature of the 

TDS unit(s) from exceeding its maximum specified rating.

 

Adequate electrical and safety protection is provided by the 

enclosure to all exposed terminals.

 

The location and type of enclosure meets the specified 

environmental requirements and prevents the ingress of moisture 

and water.

 

The indicator status of the TDS can be readily inspected.

5.  Electrical Connection 

When connecting the TDS on the input side of the distribution 

panel wiring, it is usual to wire the TDS L-N (L1, L2, L3 to N on 3 

phase systems). When connecting the TDS to the output side of 

the panel wiring, it is usual to wire it L-PE/PEN. 

 

On TN-C networks, three TDS units are required. L1, L2, L3 

should be protected to PEN. 

 

On TN-S networks, four TDS units are required.  L1, L2, L3 

should be protected to N, and N should be protected to PE.

 

On TT networks, three TDS units and a SGD unit are required.  

L1, L2, L3 should be protected to N using the TDS units, and N 

should be protected to PE using the SGD unit.

 

On IT networks, four TDS units are required. L1, L2, L3, N 

should be protected to PE using 440V TDS units on a normal 

230V system.

 

On the TDS1100 series, a “Kelvin” type connection can be 

made using separate input and output terminal pairs. This 

configuration helps reduce the effects of lead length. The 

maximum load current under such a configuration should be 

limited to 125A.

6.  Wiring

The interconnecting wiring should:

 

Be as short as possible - not exceeding 300mm (12”).

 

Avoid sharp bends >100mm radius is recommended.

 

Have the conductors twisted together where possible.

 

Terminals will allow connection of 25mm² (#4AWG) multi-

strand wiring or 35mm² (#2AWG) solid - ref. Table 1. The wire 

insulation should be stripped back 8mm (5/16").

7.  Residual Current Detectors (RCD)

When an RCD is used, it is preferable that the TDS modules be 

installed prior to (upstream of) this device to avoid nuisance 

tripping which may occur during transient activity.

8.  Fusing and Isolation

Overcurrent protection must be installed in the upstream circuit of 

every TDS unit if the mains supply is > 100A. This is to provide 

protection to the TDS, the load and the wiring in the case of a fault 

- ref. Table 1 for suitable fuse ratings.

Note:

 Operation of this over-current protection under excessive 

surge conditions may occur removing protection from the circuit. 

The Remote Status contacts should be monitored for this 

possibility.

9.  Status Indication

TDS modules incorporate an internal thermal disconnect element, 

which automatically disconnects the varistor from the network in 

the event of a thermal overload. Should the internal disconnect 

operate, a red flag appears in the transparent window of the 

status indicator(s) on the front of the TDS.

10.  Maintenance and Testing

Before removing a TDS module from service, 

ensure that the power has been removed and if 

possible “locked out”. Qualified personnel should 

only undertake replacement of TDS modules. 

Replacement plug-in modules are available. 

Note:

 It is very important to ensure that the new 

module is of the same type and voltage as that 

being replaced.

Note:

 TDS units should be inspected periodically, 

and also following any periods of lightning or 

transient voltage activity. Check the Status Indicator 

and replace the module if required.

11.  Remote Status

The TDS provides remote status monitoring via 

voltage-free contacts. Failure of the TDS is signified 

by the N/C contacts (11,14) opening and the N/O 

contacts (11,12) closing. Ensure that the voltage 

and current ratings of the contacts are not 

exceeded.

Note:

 

The TDS contacts are independent of 

whether power is supplied, or not, to the TDS 

module. The status of the contacts is given solely 

by the failure status of the TDS module.

Table 1. TDS operating specifications

TECHNICAL SUPPORT

www.erico.pentair.com

IPCR1502_A

2 OF 2

INSTRUCTION SHEET

Pentair, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by Pentair or its global affiliates. All other trademarks are

the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

© 2005-2017 Pentair All Rights Reserved

Отзывы: