Page 1
B1PF Actuator
3 Port Motorised Valve Actuator
Important: Keep this document
The B1PF range of actuators c/w auxiliary switch are specifically
designed for use in domestic applications only.
They are not designed for use in commercial or industrial
applications such as schools, nursing homes or hotels where large
commercial pump sets are fitted.
Warranty will be void If a valve is fitted in any application other
than domestic.
Please note we have a full range of commercial and industrial valves
to suit every application.
CAUTION!
Installation and connection
should only be carried out by a qualified person
and in accordance with wiring regulations.
Do not open the products. There are no serviceable
or adjustable parts inside. The system must be fused
to no more than 3 Amps.
Isolate mains supply before installation commences.
Isolate mains supply before attaching cable to
actuator.
Isolate mains supply before detaching cable from
actuator.
If this equipment is installed or used in a way not
specified by the manufacturer, its safety may be
impaired.
TECHNICAL SPECIFICATION
ACTUATOR
MANUFACTURER
MODEL
SIZE & TYPE
MAX. CLOSE OFF PRESSURE
B1PF
replacement
for
EPH
B322P(F)
22mm Compression
1.0 Bar
EPH
B328P(F)
28mm Compression
0.6 Bar
Honeywell
V4073A
22mm Compression
1.0 Bar
Honeywell
V4044C
28mm Compression
0.6 Bar
Horstmann
2322
22mm Compression
1.0 Bar
ACTUATOR
Motor supply voltage
230V
Impedance protected motor
Rated impulse voltage
2500V
Max. ambient temperature
50˚C
Power consumption
5W
Protection rating
IP20
LEAD SUPPLIED
1.2 metre cable. Earth Connection required.
ACTUATOR OPERATION
230V Power to open - Spring return to close.
This is not a fail safe, a no fail or a safety product.
This control is designated Type 1. AA. C in accordance with EN60730.
Type of action is multi position. Type of movement is rotary.
MANUAL OVERRIDE
Valve may be manually opened for filling or draining the system.
In normal operation, the lever must be in the Auto position
If the mains power is disconnected, the valve will automatically spring
return to the closed position (Port A)