Battery 
Overheating 

 

Battery level shows current value, battery frame 
blink, fault icon blink 

Load failure 

 

Load overload

  ,Load short circuit 

When  load  current  reaches1.02-1.05  times  1.05-1.25  times,  1.25-1.35  times  and 

1.35-1.5 times more than nominal value, controller will automatically turn off loads in 50s, 
30s,10s and 2s respectively

 

4.3 Load mode setting 

Operating Steps:

                                                                   

Under load mode setting interface, press SET button and hold on 5s till the number begin 
flashing, then press MENU button to set the parameter, press SET button to confirm. 

1** 

Timer 1 

2** 

Timer 2 

100 

Light ON/OFF 

2 n 

Disabled

 

101 

Load will be on for 1 hour 
since sunset 

201 

Load will be on for 1 hour 
before sunrise 

102 

Load will be on for 2 hours 
since sunset 

202 

Load will be on for 2 hours 
before sunrise 

103

113

 

Load will be on for 3

13 

hours since sunset 

203

213

 

Load  will  be  on  for  3

13 

hours before sunrise 

114 

Load will be on for 14 hours 
since sunset 

214 

Load  will  be  on  for  14 
hours before sunrise 

115 

Load will be on for 15 hours 
since sunset 

215 

Load  will  be  on  for  15 
hours before sunrise 

116 

Test mode 

2 n 

Disabled

 

117 

Manual mode(Default load 
ON) 

2 n 

Disabled

 

NOTE:  Please  set  Light  ON/OFF,  Test  mode  and  Manual  mode  via  Timer1.  Timer2 
will be disabled and display "2 n". 

4.4 Battery Type 

 

Operating Steps 

Under  Battery  Voltage  interface,  press  SET  button  and  hold  on  5s  then  enter  into  the 
interface of Battery type setting. After choosing the battery type by pressing MENU button, 
waiting for 5s or pressing SET button again to modify successfully. 

 

Battery Type 

Sealed (Default)                   

Gel                     

Flooded   

NOTE: Please refer to the battery voltage parameters table for the different battery 
type. 

5. Protections                                                                                                 

Protection 

Conditions 

Status 

PV Reverse 
Polarity 

When the battery is correct connecting, the 
PV can be reversed. 

The controller is not 
damage

 

Battery Reverse 
Polarity

 

When the PV is not connecting, the battery 
can be reversed.

 

Battery Over 
Voltage 

The battery voltage reaches to the OVD 

Stop charging 

Battery Over 
Discharge 

The battery voltage reaches to the LVD 

stop discharging 

Battery Over 
Discharge 

The battery voltage reaches to the LVD 

stop discharging 

Battery 
Overheating

 

Temperature sensor is higher than 65

 

Output is OFF 

Temperature sensor is less than 55

 

Output is ON 

Controller 
Overheating 

Temperature sensor is higher than 85

 

Output is OFF 

Temperature sensor is less than 75

 

Output is ON

 

Load Short 
Circuit 

Load current ≥2.5 times rated current

  

One short circuit, the output is OFF 5s

 

Two short circuit, the output is OFF 10s

 

Three short circuit, the output is OFF 15s

 

Four short circuit, the output is OFF 20s

 

Five short circuit, the output is OFF 25s

 

Six short circuit, the output is OFF 

Output is OFF 

Clear the fault: 

Restart the controller 
or wait for one 
night-day cycle 
(night time>3 hours).

 

Load Overload 

Load current ≥2.5 times rated current

  

1.02-1.05 times, 50s, 
1.05-1.25 times, 30s 
1.25-1.35 times,10s 
1.35-1.5 times 2s 

 

Output is OFF 

Clear the fault: 

Restart the controller 
or wait for one 
night-day cycle 
(night time>3 hours).

 

Damaged RTS   

The RTS is short-circuited or damaged 

Charging or 
discharging at 25

 

6. Troubleshooting                                                                                                 

Faults 

Possible reasons 

Troubleshooting 

The 

LCD 

is 

off 

during daytime when 
sunshine falls on PV 
modules properly 

PV 

array 

disconnection 

Confirm  that  PV  wire  connections 
are correct and tight 

Wire  connection  is 
correct, 

LCD 

not 

display 

1)  Battery  voltage  is 
lower than 9V 
2) PV voltage is less 
than battery voltage 

1)  Please  check  the  voltage  of 
battery.  At  least  9V  voltage  to 
activate the controller 
2)  Check  the  PV  input  voltage 
which  should  be  higher  than 
battery’s 

                         

Interface 
blink 

Battery over voltage 

Check  if  the  battery  voltage  is 
higher  than  OVD  point  (over 
voltage  disconnect  voltage),  and 
disconnect the PV. 

                     

Interface 
blink 

Battery   
over discharged 

When  the  battery  voltage  is 
restored  to  or  above  LVR  point 
(low  voltage  reconnect  voltage), 
the load will recover 

 

Interface                                                             
blink 

Battery Overheating   

The  controller  will  automatically 
turn  the  system  off.  But  while  the 
temperature  decline  to  be  below 
50 ºC, the controller will resume. 

                     

Interface   
blink 

Over  load  or  Short 
circuit 

Please  reduce  the  number  of 
electric  equipments  or  check 
carefully loads connection.   

8. Disclaimer                                                                                               

This warranty does not apply under the following conditions: 

1) Damage from improper use or use in an unsuitable environment.

 

2)

 

PV or load current, voltage or power exceeding the rated value of controller. 

3) User disassembly or attempted repair the controller without permission.

 

4) The controller is damaged due to natural elements such as lighting. 

5)

 

The controller is damaged during transportation and shipment. 

7.Technical Specifications                                                                                                                                                                                             

 

Item 

VS1024AU 

VS2024AU 

VS3024AU 

VS4524AU 

VS6024AU 

Nominal system voltage 

12/24VDCAuto 

Battery input voltage range 

9V

32V 

Rated charge/discharge current 

10A@55

 

20A@55

 

30A@55

 

45A@55

 

60A@55

 

Max. PV open circuit voltage 

50V 

Battery type 

Sealed(Default) / Gel / Flooded /User 

Equalize Charging Voltage

 

Sealed:14.6V/ Gel: No/ Flooded:14.8V/User:9-17V 

Boost Charging Voltage

 

Sealed:14.4V/ Gel:14.2V/ Flooded:14.6V/User:9-17V 

Float Charging Voltage

 

Sealed/Gel/Flooded:13.8V/User:9-17V 

Low Voltage Reconnect 
Voltage

 

Sealed/Gel/Flooded:12.6V/User:9-17V 

Low Volt. Disconnect 
Voltage

 

Sealed/Gel/Flooded:11.1V/User:9-17V 

Self-consumption 

≤10mA/12V;≤18mA/24V 

Temperature compensation 
coefficient 

-3mV/

/2V

25

℃)

 

Charge circuit voltage drop 

≤0.29V 

Discharge circuit voltage drop 

≤0.16V 

LCD temperature range 

-20

℃~

+70

 

Working environment 
temperature   

-25

℃~

+55

(Product can work continuously at full load) 

Humidity range 

≤95%, N.C.   

Enclosure 

IP20 

Grounding 

Common Positive 

USB input 

5VDC/2.4A 

Overall dimension 

142x85x41.5mm

 

160x94.9x49.3mm

 

181x100.9x59.8mm 

194x118.4x63.8mm                                         

214x128.7x72.2mm                                                   

Mounting dimension 

130x60mm

 

148x70mm

 

172x80mm 

185x90mm 

205x100mm 

Mounting hole size 

Φ4.5mm 

Φ5mm 

Φ5mm 

Φ5mm 

Terminals   

4mm

2

 

10mm

2

 

16mm

2

 

16mm

2

 

25mm

2

 

Net weight 

0.22kg 

0.35kg

 

0.55kg 

0.76 kg 

1.02kg 

Above the parameters are in 12V system at 25

, twice in 24Vsystem

 

 

Any changes without prior notice!   