54
automatically.)
32
Lithium
battery
protection
enable(stop
charging and
discharging
the lithium
battery when
the
temperature
is too low)
OFF
(Default)
ON
(
Note: After connecting to
the BMS successfully, it
will
be
ON
status
automatically.
)
33
Charging limit
voltage
User
define:43.2~64.0V
Step size: long-press
for 1V
,
short-press for
0.1V
AGM
(Default)
/GEL/FLD: 60.0V
LFP15: 53.5V
LFP16:57.0V
LCNM14:58.8V
35
Under
voltage
warning
reconnect
voltage
User
define:43.2~64.0V
Step size: long-press
for 1V
,
short-press for
0.1V
AGM
(Default)
/GEL/FLD: 48.8V
LFP15:48.0V
LFP16:51.2V
LCNM14:56.9V
36
Under
voltage
warning
voltage
User
define:43.2~64.0V
Step size: long-press
for 1V
,
short-press for
0.1V
AGM
(Default)
/GEL/FLD: 48.0V
LFP15:45.0V
LFP16:48.0V
LCNM14:49.0V