18
3.4 Battery Type
Operating Steps
Under Battery Voltage interface, long press ENTER button enter into the interface of Battery
type setting. After choosing the battery type by pressing SELECT button, waiting for 5 seconds
or pressing ENTER button again to modify successfully.
Battery Type
①
Sealed (Default)
②
Gel
③
Flooded
④
User(Apply to
“MT50” and “PC software “Solar Station Monitor”
)
Battery Voltage Parameters (parameters is in 12V system at 25
℃
, please use double
value in 24V.)
Battery charging setting
Sealed
Gel
Flooded
User
Over Voltage Disconnect Voltage
16.0V
16.0V
16.0V
9~17V
Charging Limit Voltage
15.0V
15.0V
15.0V
9~17V
Over Voltage Reconnect Voltage
15.0V
15.0V
15.0V
9~17V
Equalize Charging Voltage
14.6V
——
14.8V
9~17V
Boost Charging Voltage
14.4V
14.2V
14.6V
9~17V
Float Charging Voltage
13.8V
13.8V
13.8V
9~17V
Boost Reconnect Charging
Voltage
13.2V
13.2V
13.2V
9~17V
Low Voltage Reconnect Voltage
12.6V
12.6V
12.6V
9~17V
Under Voltage Warning
Reconnect Voltage
12.2V
12.2V
12.2V
9~17V
Under Volt. Warning Volt.
12.0V
12.0V
12.0V
9~17V
Low Volt. Disconnect Volt.
11.1V
11.1V
11.1V
9~17V
Discharging Limit Voltage
10.6V
10.6V
10.6V
9~17V
Equalize Duration (min.)
120
——
120
0~180
Boost Duration (min.)
120
120
120
10~180
NOTE:
1) When the battery type is sealed, gel, flooded, the adjusting range of equalize duration is 0
to180min and boost duration is 10 to180min.
2) The following rules must be observed when modifying the parameters value in user battery
type (factory default value is the same as sealed type):
a.
Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥
Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage.
b. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage
c. Low Voltag
e Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit
Voltage.
d.
Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥