Epever LS1024BPD Скачать руководство пользователя страница 2

                                                   

    BEIJING EPSOLAR TECHNOLOGY CO., LTD.                          Tel

+86-10-82894112 / 82894962        Website

www.epsolarpv.com/www.epever.com 

                                                          3                                                                                                                          4   

30s,10s and 2s respectively. 

NOTE: Just only the Load over load and the Load short circuit can be cleared by 
pressing the button. 

 

Load control setting 

(1)

 

Manual Mode 

(2) Light ON/OFF (Default)                                   
 
 
 
 
 
 
 
 
 
 

(3) Light ON +Timer   

 

 

 

 

 

 

(4)Output mode

         

The load will be on for 24 hours. The button is disabled.

 

(5)Test mode 
The same as light ON/OFF mode but no 10 minutes delay. The test mode is only used to 
test load switch. It can return to the previous mode after controller restart.

 

NOTE:  In  the  mode  of  Light  ON/OFF  and  Light  ON  +  Timer,  the  Load  is  turned  on 
after 10minutes delay.

 

 

7. Protection 

  PV Short Circuit

 

 

If the PV array short circuit, the controller will stop charging, clear it to resume normal 
operation.

 

  PV Reverse Polarity

 

 

Fully protection against PV reverse polarity, correct the wire connection to resume 
normal operation. 

  Battery Reverse Polarity 

Fully protection against battery reverse polarity, correct the wire connection to resume 
normal operation. 

  Battery Over Voltage

 

 

When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage, 
the controller will stop charging the battery to protect the battery from being over 
charged to break down. 

  Battery Over Discharge

 

 

When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage, 
the  controller  will  stop  discharging  the  battery  to  protect  the  battery  from  being  over 
discharged. 

  Battery Overheating

 

 

The  controller  detect  the  environment  temperature  through  the  external  temperature 
sensor. If the environment temperature exceeds 65 ºC, the controller will automatically 
start the overheating protection to stop working, and recover below 50 ºC. 

  Load Overload 

Load will be switched off when 1.05 times rated current overload happens. Controller will 
automatically attempt to reconnect load for 5 times. If overload protection still exist after 
controller’s 5 times attempts, user have to reduce load appliance, then press the button 
or repower the controller or wait for one night-day cycle (night time>3 hours). 

 

  Load Short Circuit 

Load will be switched off when load short circuit (

≥4 times rated current) happens. 

Controller will automatically attempt to reconnect load for 5 times. If short circuit 
protection still exist after controller’s 5 times attempts, user have to clear short 
circuit ,then press the button or disconnect and restart the controller or wait for one 
night-day cycle (night time>3 hours). 

  Controller Overheating   

If  the  Internal  temperature  of  the  controller  exceeds  85 

º

C,  the  controller  will 

automatically start the overheating protection, and recover below 75 

º

C. 

  High Voltage Transients   

The  controller  is  protected  against  small  high  voltage  transients.  In  lightning  prone 
areas, additional external suppression is recommended. 

8. Troubleshooting 

Faults 

Possible reasons 

Troubleshooting 

LED 

Charging 

indicator 

turn 

off 

during  daytime  when 
sunshine  falls  on  PV 
modules properly 

PV   
array disconnection 

Confirm  that  PV  and  battery  wire 
connections are correct and tight 

No LED indicator 

Battery voltage maybe 
less than 8V 

Measure battery voltage with the 
multi-meter. Min.8V can start up the 
controller 

Battery  LED  indicator 

Battery voltage higher 

Check  if  battery  voltage  is  higher 

green fast Flashing 

than over voltage 
disconnect 
voltage(OVD) 

than OVD, and disconnect the PV 

Battery LED indicator 

red and display 

 

” 

Battery   
over discharged 

When the battery voltage is restored 
to or above LVR point (low voltage 
reconnect voltage), the load will 
recover

 

Battery  LED  indicator 
red flashing 

Battery Overheating

 

The controller will automatically turn 
the system off. But while the 
temperature decline to be below 50 
ºC, the controller will resume. 

Charging(green)  and 
battery 

indicator 

(orange)flashing 
simultaneously

 

Controller overheating 

Please 

try 

to 

decline 

the 

environment’s  temperature,  or  the 
power of PV or the power of the load 

Load 

terminals 

no 

output 

and 

display 

 

” or “

 

 

Over  load  or  Short 
circuit

 

Please  reduce  the  number  of 
electric 

equipments 

or 

check 

carefully loads connection.   

NOTE: If want to clear errors promptly, please restart the controller and disconnect 
the  PV  array  firstly,  then  load  and  battery;  and  reconnect  system  according  to 
"Chapter4". 

9. Technical Specifications         

Item 

LS1024BPD 

LS2024BPD 

Nominal system voltage 

12/24VDC Auto 

Battery input voltage range 

8

32V 

Battery type 

Sealed (Default) / Gel / Flooded 

Max. PV open circuit voltage 

      50V 

Rated current 

10A 

20A 

Self-consumption 

9.4mA/12V;12.2mA/24V 

Charge Circuit Voltage Drop 

≤0.3V 

Discharge Circuit Voltage Drop 

≤0.2V 

Temperature compensation 

coefficient 

-3mV/

/2V 

Working environment 

temperature 

-35

℃~

+55

 

Enclosure 

IP67 

Grounding 

Common Positive 

Overall dimension 

108.5x64x25.6mm 

108.5x83x25.6mm 

Mounting dimension 

100.5mm 

100.5mm 

Mounting hole size 

Φ5

 

Power cable 

2.5mm

2

 

4.0mm

2

 

Net weight 

0.33kg 

0.41kg 

Battery Voltage Control Parameters 

Below parameters are in 12V system at 25 ºC, please double the values in 24V system 

Battery Type   

Sealed 

Gel 

Flooded 

Over Voltage Disconnect Voltage 

16.0V 

16.0V 

16.0V 

Charging Limit Voltage 

15.0V 

15.0V 

15.0V 

Over Voltage Reconnect Voltage 

15.0V 

15.0V 

15.0V 

Equalize Charging Voltage 

14.6V 

—— 

14.8V 

Boost Charging Voltage 

14.4V 

14.2V 

14.6V 

Float Charging Voltage 

13.8V 

13.8V 

13.8V 

Boost Reconnect Charging Voltage 

13.2V 

13.2V 

13.2V 

Low Voltage Reconnect Voltage 

11.6V 

11.6V 

11.6V 

Under Voltage Warning Reconnect 

Voltage 

12.2V 

12.2V 

12.2V 

Under Voltage Warning Voltage 

12.0V 

12.0V 

12.0V 

Low Voltage Disconnect Voltage 

11.1V 

11.1V 

11.1V 

Discharging Limit Voltage 

10.6V 

10.6V 

10.6V 

Equalize Duration 

120 min. 

—— 

120 min. 

Boost Duration 

120 min. 

120 min. 

120 min. 

10. Disclaimer 

 

Damage from improper use or use in an unsuitable environment.

 

  PV or load current, voltage or power exceeding the rated value of controller. 

 

User disassembly or attempted repair the controller without permission.

 

  The controller is damaged due to natural elements such as lighting. 

  The controller is damaged during transportation and shipment. 

 
 
 
 

A

ny changes without prior notice!   

Version number

V2.1 

     

 

Отзывы: