2. Battery connection
CAUTION
A fuse must be installed on the battery side, conformed to the following requirements.
1. Fuse voltage is 1.5 to 2 times the inverter's rated voltage.
2. Fuse current is 2 to 2.5 times the inverter's rated current.
3. Distance between the fuse and the battery cannot be farther than 150mm.
3. AC loads connection
WARNING
The AC loads shall be determined by the continuous output power of the inverter.
The surge power of the AC load must be lower than the instantaneous surge
power of the inverter, or the inverter will be damaged.
The N pole of the AC output port cannot be grounded. If grounding the N pole is
necessary, please purchase the IPower-Plus-B series.
1) Definition of the AC output port
It varies with different product models; please refer to the actual product. The following takes the AC
terminal as an example.