| RT Series True Online UPS
3. Installation
• Open the UPS package and inspect the contents upon receipt. The accessories attached to the UPS contain
a power cord, a user manual, communication cable, CD-ROM. The long backup model also includes the
cable for connection to battery bank.
• Check if the unit is damaged during transport. Do not power on and notify the carrier and dealer if find
damaged or parts missing.
• Verify this unit is the model you want to buy. Check the model name showed both on the front panel and
rear panel.
• The UPS installation environment must be in good ventilation, away from water, flammable gases and
corrosive entities.
• Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake
hole will be unobstructed.
• The ambient temperature around the UPS should be within 0 ~ 40°C (non-condensing).
• If dismantling the machine at low temperatures, there may be condensation droplets, users can not install
or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of
electric shocks.
• Place the UPS near the mains source so that can cut off utility power without any delay in case of
emergency.
• Make sure the load connected to the UPS is off when users connect it to UPS, and then turn on the load one
by one later.
• Connect the UPS with the power outlet which is over-current protected. Do not connect the UPS with
power outlets whose rated current is less than the maximum input current of this UPS.
• All power outlets should be configured with earthing device for safety.
• UPS could be electrified or powered no matter the input power cord is tied or not, even when the UPS is off.
The only way to cut off the output is switching off the UPS and disconnecting the mains power supply.
• For all standard model UPS, it is advised to charge the batteries over 8 hours before using. Once the AC
mains power energizes the UPS, it will automatically charge the batteries. Without prior charging, UPS
output remains as usual but with shorter back-up time than normal.
• When connected to motor, display equipment, laser printer etc, UPS power selection should be based on
the startup power of the load which is usually twice as rated power.
• Wiring by a qualified electrician is required. Ensure input cables and output cables are connected correctly
and firmly.
• If install a leakage current protective switch, please install it on output cable.
• For 1-3K series long backup model units, you may need to prepare wires for terminals based on the
following table.
3.1 Unpacking Inspection
3.2 Installation Information
Keep the packaging box and packaging materials for future transport use.
The equipment is heavy. Always handle it with care.
Note: