Relay Box for Infrared Cabins - Installation Instructions
17
Installation
Extending the control unit's control line
The control line may be extended to approx. 100 m, if necessary.
The maximum line length for the EmoTouch 3 control unit is 25 m. For extra
long connections, special RJ10/RJ14 connecting lines with a length of
10 m, 25 m, 50 m and 100 m are available as an option.
Alternately, the 5-m line can also be extended with an RJ12/RJ12 coupling
and an RJ12/RJ12 extension cord (optional accessory).
If the line length is greater than 25 m, a special bus amplifier (accessory)
with power supply must also be installed near the control unit and con-
nected to it. The bus amplifier requires a 230-V mains connection.
4.2 Installation work inside the cabin
At minimum, the cabin lighting and a temperature sensor must be
installed inside the cabin. Additional connections are possible, depending
on the amenities, e.g. coloured lights and audio systems as optional add-
on modules.
Example – cabin
The position and number of IR emitters and foils (IR emitters) can vary
depending on the design of the cabin.
The temperature sensor must be installed where expected temperatures
are the highest. In an infrared cabin, this is typically at the centre of the
cabin ceiling.
A
Temperature sensor
B
IR foil (installed inside the wall)
C
IR emitter
A
C
B