5.1 Scheduled Maintenance

Marvair

®

 strongly recommends that the heat pump be serviced a minimum of once a year.  At 

this time the filter, evaporator coil, condenser coil, the cabinet, and condensate drains should be 

serviced as described below.  Also at this time, the heat pump should be operated in the cooling 

and heating cycles as described in Chapter 3, Start-Up.  In addition to this seasonal check-out, 

the Enviromax™ HP should be maintained as follows:

Air Filter

Replace the air filter whenever it is visibly dirty.  

Evaporator

If the evaporator becomes clogged or dirty, it may be cleaned by careful vacuuming or with a 

commercial evaporator cleaning spray.  DO NOT use a solvent containing bleach, acetone, or 

flammable substances.  Turn power off before cleaning.  Be careful not to wet any of the electrical 

components.  Be sure the unit has dried before restarting.

Condenser

Periodically inspect the outdoor condenser coil and the cabinet air reliefs for dirt or obstructions.  

Remove  foreign objects such as leaves, paper, etc. 
If the condenser coil is dirty, it may be washed off with a commercial solvent intended for this 

purpose.  TURN OFF POWER BEFORE CLEANING!  Be sure that all electrical components 

are thoroughly dry before restoring power.

Cabinet

The cabinet may be cleaned with a sponge and warm, soapy water or a mild detergent.  Do not 

use bleach, abrasive chemicals or harmful solvents. 

Drains

Regularly check the drain, the upper condensate pan the lower drain pan and the sump. The con-

densate produced during the cooling cycle collects in the upper pan and flows through tubing into a 

sump located beneath the lower coil. In the heating mode, water produced during the defrost cycle 

flows directly into the sump. A pump, located in the sump, pumps the water out of sump, through 

tubing to the side of the Enviromax heat pump. Check to see that all drain pans, interconnecting 

tubing are free of any debris and water flows freely.  If a commercial drain solvent is used, flush 

out the drain pan and system with plenty of fresh water to prevent corrosion..

5.2 Winter Storage

If the Enviromax heat pump is to be stored in a site where temperatures can drop to 0ºC or lower, 

water in the sump may freeze and damage the pump. To prevent damage to the pump, remove the 

drain plug located at the bottom of the sump and allow the water to drain from the sump. Replace 

the drain plug after all water is removed from the sump.

Maintenance

Содержание AVMC36HPWN

Страница 1: ...rton Canes Cannock Staffordshire United Kingdom WS11 9UU 44 0 1543 459 974 Fax 44 0 1543 450 737 E mail sales enviromax co uk Internet www enviromax co uk Manufactured under U S Patent No 6 571 572 No...

Страница 2: ...UNIT UPRIGHT Laying it down on its side may cause oil to leave the compressor resulting in DAMAGE upon START UP 3 TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on t...

Страница 3: ...ut of Cooling Cycle 14 3 2 Check Out of Heating Cycle 14 Troubleshooting 4 1 Overview 15 4 2 Failure Symptoms Guide 16 4 3 Compressor Troubleshooting 17 Periodic Maintenance Requirements 5 1 Scheduled...

Страница 4: ...hanges to the Enviromax 10 heat pump include 1 The use of a single larger capacity condensate pump instead of two smaller pumps 2 The wire harnesses connecting the control board to the internal thermo...

Страница 5: ...ill enter into and indicate the lockout mode In the lockout mode the compressor is turned off If there is a call for indoor air flow G the blower remains energized the alarm output is energized and th...

Страница 6: ...CRIPTION GREEN POWER CONSTANT ON 24 VAC POWER HAS BEEN APPLIED RED STATUS CONSTANT ON NORMAL OPERATION 1 BLINK HIGH PRESSURE SWITCH HAS OPENED TWICE 2 BLINKS LOW PRESSURE SWITCH HAS OPENED TWICE LEDs...

Страница 7: ...et Coil Table 2 Filter Size mm 1 2 Ratings Specifications MODEL 0 25 Pa 0 50 Pa 0 75 PA 36 1580 1425 1270 CFM Cubic Feet per Minute Indoor Air Flow ESP External Static Pressure Pa m3 hr MODEL DESCRIPT...

Страница 8: ...ycle Figure 1 Refrigerant Circuit Heating Mode During heating mode a special reversing valve reverses the flow of refrigerant through the sys tem exchanging the roles of the condenser and evaporator N...

Страница 9: ...Enviromax 12 06 Figure 2 Typical Electric Schematic for Models AVMC36 1 4 Electrical Diagrams The compressor is energized with a contactor controlled by a 24 VAC pilot signal see Figure 2...

Страница 10: ...10 Enviromax 12 06 Figure 3 Electrical Box for Models AVMC36...

Страница 11: ...s Airflow entering the outdoor coil from either side and exiting the coil from the front must not be hindered or obstructed A minimum clearance of 600 mm is recommended from the front of the unit for...

Страница 12: ...o 245 volts They are factory wired for operation on a 221 volt to 245 volt power supply To determine the voltage at your site using a voltage meter carefully measure the voltage at the end of the powe...

Страница 13: ...e water pump is located beneath the outdoor coil in a sump Water produced during the defrost cycle collects in the lower pan and flows into the sump Condensate from the upper pan flows directly into t...

Страница 14: ...cled 3 To stop cooling slowly raise the thermostat set point to a temperature higher than the ambi ent If the unit fails to operate refer to the troubleshooting information in Chapter 4 Follow the sam...

Страница 15: ...e wires crimped tubing missing parts etc Begin deeper analysis only after making this initial inspection The troubleshooting information in this manual is basic The troubleshooting section contains pr...

Страница 16: ...igerant circuit 3 Refrigerant overcharge following field service 1 Check blower assembly for proper operation Look for airflow restrictions e g the air filter Check blower motor and condenser fan 2 Ch...

Страница 17: ...amperage stays high check the motor winding resistances NOTE Feel the top of the compressor to see if it has overheated If it is hot the internal overload may be open You may have to wait several hou...

Страница 18: ...tended for this purpose TURN OFF POWER BEFORE CLEANING Be sure that all electrical components are thoroughly dry before restoring power Cabinet The cabinet may be cleaned with a sponge and warm soapy...

Страница 19: ...mm x 395mm x 25mm 80136 Compressor Jacket Optional 20044 Switch Toggle DPDT for selecting voltage 70027 Block Terminal Light Gray 80520 Three Link Siemens 500 MM Long Strip 80522 Plug Siemens 1 Pin 80...

Отзывы: