17
Rain cap - ensure cap is at
least 2 feet (610mm) above
the roof at the lowest point
Storm collar
Roof flashing
Roof rafter
Fire stop with
Support Collar
Ceiling joist
Vertical vent pipe
Clean out tee with
Pipe adapter
NOTE:
All vent sections must maintian 3"
(76 mm) clearances to combustibles.
Installation
i
nSide
v
ertical
i
nStallationS
- f
reeStanding
:
1. Choose a stove location that is ideal. See the section “
I
nStallatIon
- d
eCIdIng
W
Here
to
l
oCate
your
P
ellet
a
PPlIanCe
.”
Figure 22: Inside Vertical Installation.
2. Place the unit on the
hearth pad (if installed on
a carpeted surface) and
space the unit in a manner
so when the pellet vent is
installed vertically, it will be
3” (76 mm) away from a
combustible wall.
3. Locate the center of the
fresh air intake pipe on the
unit. Match that center with
the same point on the wall
and cut a hole about 2” (51
mm) in diameter.
4. Install the fresh air intake
pipe.
5. Install the tee with clean
out.
6.
I
nstall the pellet vent
upward from there. When
you reach the ceiling, make
sure that the vent goes
through the ceiling fire stop.
Maintain a 3” (76 mm)
distance to combustibles
and keep attic insulation
away from the vent pipe.
Maintain an effective vapor
barrier.
7. Finally, extend the pellet
vent to go through the roof
flashing.
8. Ensure that the rain cap
is approximately 24” (610
mm) above the roof.