9

hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.

3.  Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be 

installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the 

possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a 

nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred 

venting method is to extend the vent through the roof vertically.

4.  Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the 

plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located 

in the vicinity of termination. The grade surface must not be lawn.

5.  If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior 

of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no 

guarantee against such incidents.

NOTE: Venting terminals shall not be recessed into walls or siding.

Installation

v

ent

 t

ermination

 r

equirementS

:

IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER. 

Figure 6: Use in conjunction with Table 2 for allowable exterior vent termination 

locations. 

Table 2: Use in conjunction with Figure 6 for allowable exterior vent termination locations. 

Letter

Minimum Clearance

Description

A

24 in (61 cm)

Above grass, top of plants, wood, or any other combustible materials.

B

48 in  (122 cm) 

Beside/below any door or window that may be opened. (18” (46 cm) if outside 

fresh air installed.) 

C

12 in (30 cm)

Above any door or window that may be opened. (9” (23 cm) if outside fresh air 

installed.) 

D

24 in (61 cm)

To any adjacent building, fences and protruding parts of the structure.

E

24 in (61 cm)

Below any eave or roof overhang

F

12 in (30 cm)

To outside corner.

G

12 in (30 cm)

To inside corner, combustible wall (vertical and horizontal terminations).

H

3 ft (91 cm) within a height 

of 15 ft (4.5 m) above the 

meter/regulator assembly

To each side of center line extended above natural gas or propane meter/

regulator assembly or mechanical vent.

I

3 ft (91 cm)

From any forced air intake of other appliance

J

12 in (30 cm)

Clearance to non-mechanical air supply inlet to building, or the combustion air 

inlet to any appliance.

K

24 in (61 cm)

Clearance above roof line for vertical terminations.

L

7 ft (2.13 m)

Clearance above paved sidewalk or paved driveway located on public property.

Air Supply Inlet

Gas Meter

Restriction Zone

(Termination not allowed)

Termination Cap

G

G

Opens

Opens

Opens

D

F

B

B

A

I

H

K

G

G

L

C

E

1. Do  not  terminate  the 

vent  in  any  enclosed  or 

semi-enclosed  areas  such 

as  a  carport,  garage, 

attic,  crawlspace,  narrow 

walkway,  closely  fenced 

area,  under  a  sundeck 

or  porch,  or  any  location 

that  can  build  up  a 

concentration  of  fumes 

such as stairwells, covered 

breezeway, etc.

2.  Vent surfaces can become 

Содержание M-55C-FS

Страница 1: ...E TECHNICAL MANUAL PELLET STOVE M 55C FS PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET BURNING ROOM HEATER FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAM...

Страница 2: ...haust And Fresh Air Intake Locations 10 Mobile Home Installation 11 Corner Through Wall Installation 11 Horizontal Exhaust Through Wall Installation 12 RECOMMENDED Through Wall With Vertical Rise and...

Страница 3: ...ce shows how often you need to clean to be safe OPERATION The door and ash drawer must be kept closed when the unit is in operation to prevent fume spillage and for proper and safe operation of the pe...

Страница 4: ...bearing capacity if existing construction doesn t meet load capacity suitable measures e g load distributing plate must be taken to achieve it DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYST...

Страница 5: ...de d gagement requis pour le mod le FS qu il soit encastr sur pied ou dans une maison mobile Sidewall to Unit Du mur de c t l appareil A 9 in 230 mm Backwall to Unit Du mur de derri re l appareil B 3...

Страница 6: ...ble 1 M 55C FS Specifications Description Fuel type Residential Pellet Heater 6mm dia Pellets wood corn wheat barley Voltage Current Max Power 110 120 V 4 2 Amps 504 Watts Frequency Hopper Capacity Co...

Страница 7: ...to carpet If it is to be installed on a carpeted area a solid surface wood metal or approved hearth pad must be installed between the unit and the carpet 6 This unit uses large quantities of air for c...

Страница 8: ...hermostat Installation 1 Install the wall thermostat millivolt rated thermostat recommended or a 12 24 Volt rated thermostat set to millivolts in a location that is not to close too the unit but will...

Страница 9: ...rmination locations Table 2 Use in conjunction with Figure 6 for allowable exterior vent termination locations Letter Minimum Clearance Description A 24 in 61 cm Above grass top of plants wood or any...

Страница 10: ...ight homes and mobile homes When connecting to an outside fresh air source do not use plastic or combustible pipe A 3 minimum 76 mm ID inside diameter steel aluminum or copper pipe or ducting should b...

Страница 11: ...estal Ensure the unit is electrically grounded to the chassis of your home permanently Do not install in a room people sleep in Outside fresh air is mandatory Secure outside air connections directly t...

Страница 12: ...fastened with at least three 3 screws 1 Place the appliance 15 37 5 cm away from the wall If the stove will be installed a hearth pad set the unit on it 2 Locate the center of the exhaust pipe on the...

Страница 13: ...installations have 3 to 5 feet 91 to 152 cm of vertical pipe in the system to help naturally draft the unit in the event of extreme weather or a power outage Some horizontal through wall installations...

Страница 14: ...Vertical section of vent pipe Horizontal frame for thimble 90o elbow Concrete Wall Clean out tee Installation to use if there is a concrete or retaining wall in line with exhaust vent on pellet stove...

Страница 15: ...Installations section and then finish it by performing the following refer to Figure 15 1 Install a tee with clean out on the outside of the house 2 Install PL vent upward from the tee Make sure that...

Страница 16: ...o when the pellet vent is installed vertically it will meet the minimum clearance from a combustible wall stated by the vent manufacturer 2 Install the tee with clean out 3 Install the pellet vent upw...

Страница 17: ...chimney If holes already exist fresh air intake can be taken through back of the fireplace or through the ash dump Installation Hearth Mount Installation Figure 17 Hearth Mount Side View Figure 18 He...

Страница 18: ...Feed Trim and Fuel Type Functions can be used to compensate for varying fuel qualities Refer to the Owners Manual for circuit board operation If after long periods of burning the fire builds up or th...

Страница 19: ...or If the 3 light is flashing unit may be out of fuel Check the Door and Ash Pan door THEY MUST BE CLOSED TIGHT See section 8 The Fuel will not light Check the fuse on the circuit board If the unit st...

Страница 20: ...vertical section to move termination into a low pressure zone To reset Circuit Board after a trouble code push the ON OFF button 5 Unit is on but auger motor does not turn at all Check the line fuse...

Страница 21: ...s going out If the stove goes out and leaves fresh unburned fuel in the burn pot liner the fire is going out before the stove shuts off Trim the combustion air down to decrease the magnahelic pressure...

Страница 22: ...or Grey Grey Orange Orange White Grey Grey White Blue Yellow Auger Motor White Yellow Vacuum Switch Connect Thermostat Here Brown Brown Blue Purple Yellow Red Thermostat Combustion Blower Black Black...

Страница 23: ...5 AGITATOR DRIVE BRACKET 50 2038 16 SS BURN POT LINER 50 2042 17 EXHAUST STARTER TUBE CW GASKET 50 2043 18 CAST FLUTED FIREBOX LINER 50 2048 19 HOPPER SWITCH 50 2052 20 EXHAUST MOTOR CAPACITOR C W STR...

Страница 24: ...50 2114 37 M55C FS CAST LEG LIP RIGHT BEACH 50 2126 37 M55C FS CAST LEG LIP RIGHT CHESTNUT 50 2134 40 M55C FS CAST ASH DOOR 50 2115 38 M55C FS CAST ASH DOOR BEACH 50 2127 38 M55C FS CAST ASH DOOR CHES...

Страница 25: ...25 Parts Diagram Components 26 22 48 19 54 1 52 55 2 53 23 25 10 44 32 33 11 24 4 9 6 3 12 21 20 40 50 31 39 42 47 15 8 7 49 56 43 51 5 14 16 27 46 17 45...

Страница 26: ...Parts Diagram CAST 26 30 18 28 35 37 13 29 38 36 34...

Страница 27: ...epair or replacement for the first two 2 years and limited labour for the first two 2 years to the original purchaser Please see the exclusions and limitation section below as certain restrictions and...

Страница 28: ...ify the Limited Warranty on this stove If unsure as to the extent of this Limited Warranty contact your authorized Enviro dealer before installation 10 Sherwood Industries Ltd will not be responsible...

Страница 29: ...nt schedule Labour rates are set per component and as such total labour costs may not be covered 26 Sherwood Industries Ltd is not liable for freight or labour on any stove replaced in field and is no...

Страница 30: ...AL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy MAGNEHELIC AT INSTALL ___________________ INSTALLER S SIGNATURE ____________...

Отзывы: