ET3-M SMART DEMAND URINAL FLUSH VALVE TROUBLESHOOTING YOUR INSTALLATION

 

 

Initial Checks 

 

 

C

HECK WATER SUPPLY

;

 

 

 

U

NPLUG  ALL  CABLES

,

 

(

TAKING  CARE  TO  UNSCREW  ALL  CONNECTIONS  FULLY  PRIOR  TO 

DISCONNECTION

)

  LEAVE UNPLUGGED FOR 

5

 MINUTES

 (

THIS GIVES THE ELECTRONICS A CHANCE TO 

RESET

BEFORE  RECONNECTING  EVERYTHING  CAREFULLY  IN  THE  CORRECT  ORDER 

(

SEE  DIAGRAM 

BELOW

)

 

W

ARNING 

-

  ELECTRONICS  WILL  BE  DAMAGED  IF  CONNECTED  OR  DISCONNECTED 

INCORRECTLY

 

E

NSURE SCREWED COLLAR CONNECTIONS ARE TIGHT 

(

DO NOT OVERTIGHTEN

);

 

 

 

I

F URINAL HAS BEEN OPERATING CORRECTLY FOR SOME TIME

 AND HAS SUDDENLY STOPPED 

 LIKELY 

CAUSE IS NO POWER

.

 TO CONFIRM 

-

 CHANGE BATTERIES

,

 UNIT SHOULD FLUSH

.

 CHECK MAINS POWER 

SUPPLY

/

HOTPOINT AS FLUSH VALVE  MUST BE MAINS POWERED WITH BATTERY BACK

-

UP

;

 IT IS NOT 

DESIGNED TO RUN ON BATTERY ONLY

 

I

F NEW INSTALLATION

 

-

 CHECK THAT IT HAS BEEN INSTALLED CORRECTLY

,

 IN ACCORDANCE WITH THE 

INSTALLATION MANUAL

.

 

 

 

 

^

I

N

-

CEILING INSTALLATIONS 

 FLUSH VALVE MUST BE INSTALLED VERTICALLY

.

 COPPER PIPE MUST BE 

USED BETWEEN SOLENOID AND URINAL

;

 IT MUST BE VERTICAL AND STRAIGHT

.

 CHECK THAT NO FLEXI

-

HOSE HAD BEEN USED AND THERE ARE NO BENDS

/

KINKS OR HORIZONTAL SECTIONS OF PIPEWORK

.

 

INCORRECT  INSTALLATION  CAN  SLOW

/

IMPEDE  THE  FLOW  OF  WATER  FROM  THE  SOLENOID  TO  THE 

URINAL AND OVER THE SENSOR ACTIVATION ZONE

,

 CAUSING RE

-

FLUSH ONCE CONFIRMATION TIME IS 

COMPLETE

.

 IF PROBLEMS PERSIST 

 CONSIDER INSTALLATION OF AIR

-

BREAK VALVE 

(

RECOMMENDED

).

  

 

 

 