Envirco MAC 10 VE5 RSR Скачать руководство пользователя страница 1

 

Updated 7/05 

*** READ AND SAVE THESE INSTRUCTIONS *** 

 

 
 
                                             

        

 

MAC 10

 

Original 

VE5

 FAN FILTER MODULE 

INSTALLATION AND SERVICE MANUAL

 

 

STANDARD, RSR, RSRE MODELS

 

 

 

 

 

                       
 Mac 10

 and VE5

 are registered Trademarks of the 

 Envirco Corporation, Albuquerque, New Mexico, U.S.A.   
 
 

US Patents 4,560,395 and 5,470,363 Other patents issued and pending in foreign countries

 

 

Содержание MAC 10 VE5 RSR

Страница 1: ...E5 FAN FILTER MODULE INSTALLATION AND SERVICE MANUAL STANDARD RSR RSRE MODELS Mac 10 and VE5 are registered Trademarks of the Envirco Corporation Albuquerque New Mexico U S A US Patents 4 560 395 and...

Страница 2: ...rer If you have any questions contact the manufacturer ENVIRCO CORPORATION FEDDERS INTERNATIONAL Envirco Office Headquarters 5601 Balloon Fiesta Parkway N E No 728 Fuzhou Road Albuquerque New Mexico 8...

Страница 3: ...II SERVICE REMOVAL AND INSTALLATION OF THE ROOM SIDE REPLACEABLE FILTER RSR RSRE 5 IV SERVICE REMOVAL AND INSTALLATION OF THE MOTOR STANDARD AND RSR MODELS 7 V SERVICE REMOVAL AND INSTALLATION OF THE...

Страница 4: ...prefilter is recommended every three to six months Step 1 To gain access to the prefilter remove the ceiling panel next to the unit if applicable Step 2 Switch the ON OFF switch to the off position S...

Страница 5: ...lding the HEPA ULPA filter to the lid assembly Step 3 Lift the lid assembly off the HEPA ULPA filter see Figure 2 Discard the used filter as per requirements of the applicable regulations Note Before...

Страница 6: ...ve the six screws and clips remove filter blocks and lower the filter as shown in Figure 3 Step 4 Inspect filter for visible damage if damaged set aside for replacement or repair Step 5 Place the filt...

Страница 7: ...MAC 10 Original VE5 SERVICE MANUAL PAGE 6 Figure 4 4 1 2 3 5 6...

Страница 8: ...t off cover Step 5 Make note of all wire locations for reinstallation later Step 6 Disconnect the two brown wires from the capacitor using a pair of pliers Step 7 Disconnect the motor wiring from the...

Страница 9: ...MAC 10 Original VE5 SERVICE MANUAL PAGE 8 Figure 5 Disconnect motor leads from capacitor ON OFF switch and three speed switch or speed control Prefilter Motor Venturi Ring Blower Wheel...

Страница 10: ...hile supporting the baffle assembly from below remove the four corner screws on the baffle assembly and lower the assembly see Figure 6 Step 3 Prior to removing motor blower assembly remove electrical...

Страница 11: ...oval of the motor mount bracket measure the precise location of the bracket on the motor Remove the bracket Step 7 Replace with the new motor and reassemble by reversing the above steps Set the locati...

Страница 12: ...ould be conducted to determine the filter condition and appropriate fan speed setting Figure 8 Optional Speed Control Units furnished with the optional speed control the speed control is standard with...

Страница 13: ...oltage amperage and distribution frequency Step 5 Replace HEPA ULPA filter if the air velocity remains low High Air Velocity Step 1 Flip switch from HIGH to MEDUIM to LOW on units with 3 speed switch...

Страница 14: ...10 Original VE5 SERVICE MANUAL PAGE 13 VIII MAC 10 VE5 Wiring Diagrams Figure 10 Figure 11 Standard Wiring for MAC 10 ON OFF switch Speed Control 10 Capacitor Optional Wiring for MAC 10 With Speed Con...

Страница 15: ...Standard Filter HEPA ULPA Optional 2 x 2 1 69514 004 69514 018 2 x 3 1 69514 019 69514 012 2 x 3 5 1 69514 020 69514 021 2 x 4 1 69514 006 69514 007 HEPA Filter RSR 2 x 2 1 69391 005 69391 006 2 x 3 1...

Страница 16: ...ny other commercial loss This warranty excludes certain expendable items such as light tubes prefilters etc ENVIRCO expressly disclaims and excludes from this warranty any responsibility for equipment...

Страница 17: ...MANUAL PAGE 16 cleanroom start up may be time consuming and recommends using 3 Velgrid readings taken on a diagonal as shown below Recommended Testing 8 readings with a Velgrid Factory Approved Testin...

Отзывы: