Shenzhen Envicool Technology Co., Ltd.
Condensate
discharge
Conduct visual check whether the condensate water
drainage is smooth, and whether there is foreign
material to block the drainage paths.
6 months
condensate
water
processor
Conduct visual check whether there is mud or other
foreign material inside the condensate water
processor tank, which should be removed and
cleaned with wet cloth.
6 months
Condenser
Check the cleanness of the condenser and clean it
with compressed air
6 months
Air filter
Conduct visual check whether there is dust or other
dirty plugging on the strainer surface, which should
be pulled out and cleaned with compressed air. In
case of damage, the strainer should be timely
replaced.
3 months
5.1.1 Condensate discharge
CAUTION!
The condensate mast be able to run off freely. If the condensate is to be drained off over a greater distance,
then care must be taken that the hose is free from kinks and a check for correct drainage made.
the extension pipe connection is not allowed
(
Hose specification see attached list.
)
.As shown in figure
④
The steps are as follows:
①
.
Open the plastic panel;
②
.
Sheathe the hose clamp and fasten with straight screwdriver;
③
.
The pipe assembly is ready.
500-2000W units:
4000W units:
EIA series air conditioner user manual